77 Ill. Adm. Code 330.3000
Mechanical Drawings
Section 330
Section 330.3000Â Mechanical
Drawings
Mechanical drawings shall
include:
a)Â Â Â Â Â Â Â Â These drawings with specifications shall show the complete
heating, steam piping, ventilation and air conditioning systems; plumbing,
drainage and stand pipe systems; laundry and kitchen ventilation.
b)Â Â Â Â Â Â Â Â Heating, steam piping, air conditioning and ventilation
including:
1)Â Â Â Â Â Â Â Â Radiators and steam heated equipment, such as sterilizers,
warmers, and steam tables.
2)Â Â Â Â Â Â Â Â Heating and steam mains and branches with pipe sizes.
3)Â Â Â Â Â Â Â Â Diagram of heating and steam risers with pipe sizes.
4)Â Â Â Â Â Â Â Â Sizes, types and heating surfaces of boilers; furnace with
stokers and oil burners, if any.
5)Â Â Â Â Â Â Â Â Pumps, tanks, boiler breeching, piping and boiler room
accessories.
6)Â Â Â Â Â Â Â Â Air conditioning systems with required equipment, water and
refrigerant piping and ducts.
7)Â Â Â Â Â Â Â Â Supply and exhaust ventilating systems with necessary duct
work and piping.
8)Â Â Â Â Â Â Â Â Air quantities for all room supply and exhaust ventilating
duct openings.
c)Â Â Â Â Â Â Â Â Plumbing, drainage, and stand pipe systems including:
1)Â Â Â Â Â Â Â Â Size and elevation of street sewer, house sewer, house drains,
street water main, and water service into the building.
2)Â Â Â Â Â Â Â Â Location and size of soil, waste, and vent stacks with
connections to house drains, clean outs, fixtures, and equipment.
3)Â Â Â Â Â Â Â Â Size and location of hot, cold, and circulating mains,
branches, and risers from the service entrance and tanks.
4)Â Â Â Â Â Â Â Â Riser diagram to show all plumbing stacks with vents, water
risers, and fixture connections.
5)Â Â Â Â Â Â Â Â Gas, oxygen, and special connections.
6)Â Â Â Â Â Â Â Â Stand pipe and sprinkler systems.
7)Â Â Â Â Â Â Â Â Plumbing fixtures and fixtures which require water and drain
connections.