77 Ill. Adm. Code 330.3080
Corridors
Section 330
Section 330.3080Â Corridors
Every building shall meet the
following requirements:
a)Â Â Â Â Â Â Â Â All corridors used by residents shall have a minimum
unobstructed width of six feet and lighted properly at night and all other
times when necessary. If handrails project more than three and one-half
inches, the width shall be measured between handrails. Â (B)
b)Â Â Â Â Â Â Â Â Corridors used by residents shall be enclosed and have a
minimum ceiling height of seven feet eight inches. (B)
c)Â Â Â Â Â Â Â Â Corridors and passages used by residents shall have sturdy
handrails one and one-half inches in diameter and be at least one and one-half
inches clear of the wall. (B)
d)Â Â Â Â Â Â Â Â Enclosed corridors shall be properly heated.
e)Â Â Â Â Â Â Â Â Corridors shall not be used to supply air to or exhaust air
from any room, except that exhaust air from corridors may be used to ventilate
rooms such as bathrooms, toilet rooms, or janitor's closets which open directly
on corridors.
f)Â Â Â Â Â Â Â Â For exit corridors, see Section 330.3380.