77 Ill. Adm. Code 330.3160
Plumbing
Section 330
Section 330.3160Â Plumbing
a)Â Â Â Â Â Â Â Â Every building shall meet the following plumbing requirements:
1)Â Â Â Â Â Â Â Â Comply with the Department's rules entitled "Illinois
Plumbing Code" (77 Ill. Adm. Code 890). (A, B)
2)Â Â Â Â Â Â Â Â All plumbing shall be of adequate size and so installed that
fixtures receive water under good pressure and are satisfactorily drained.
3)Â Â Â Â Â Â Â Â All plumbing fixtures having connections to the building water
supply shall be connected or equipped so as to prevent any back flow of
contaminated material to the water supply piping. (A, B)
4)Â Â Â Â Â Â Â Â Individual sewer connections shall be such that backflow
cannot occur from the building sewer to the fixture. (A, B)
5)Â Â Â Â Â Â Â Â No physical connection shall be permitted between a safe and
an unsafe water supply. (A, B)
b)Â Â Â Â Â Â Â Â The following standards shall be used as a guide to determine
satisfactory compliance of individual fixtures:
1)Â Â Â Â Â Â Â Â Lavatory faucets shall discharge at least one inch above the
top rim of the lavatory bowl. (B)
2)Â Â Â Â Â Â Â Â Bathtub, sink, laundry, and tub faucets shall discharge at
least two inches above the top rim of the sink. (B)
3)Â Â Â Â Â Â Â Â Flush tank type toilets shall be equipped with approved
antisiphon ball cocks, so installed that the effective air openings of the
vacuum breaker is at least one inch above the top of the overflow tube in the
toilet flush tank. (B)
4)Â Â Â Â Â Â Â Â Flushometer type toilets shall be equipped with approved
vacuum breakers, installed on the discharge side of the flush valve, and at
least four inches above the top of the toilet bowl. (B)
5)Â Â Â Â Â Â Â Â Dishwashing machines, laundry machines, urinals, and drinking
fountains shall be so installed as to provide backflow protection. (B)
6)Â Â Â Â Â Â Â Â All fixtures having, or capable of receiving, a hose shall
have a vacuum breaker located at least six inches above the highest head that
normally may be placed on the unit. The height of the antisiphon unit should
be sufficient to prevent any pressure on the unit, other than atmospheric
pressure, when the control valve is closed. (B)
7)Â Â Â Â Â Â Â Â Potable water shall be protected from cross connections to
sewage piping systems, boilers, and other sources of contaminated water. (B)
8)Â Â Â Â Â Â Â Â Hot water distribution systems shall be arranged to provide
hot water of at least 100 degrees Fahrenheit at each hot water outlet at all
times.
9)Â Â Â Â Â Â Â Â Hot water available to residents at shower, bathing and
handwashing facilities shall not exceed 110 degrees Fahrenheit. (A, B)
10)Â Â Â Â Â Â Â Â Each hot water system serving resident areas shall include at
least one of the following equipment requirements to insure that the water
temperature does not exceed 110 degrees Fahrenheit:
A)Â Â Â Â Â Â Â A thermostatically controlled mixing valve, or
B)Â Â Â Â Â Â Â An aquastat which limits the water temperature in the water
heater to a maximum temperature of 110 degrees Fahrenheit and a solenoid
operated shut off valve activated by a sensing element in the water line which
shuts off the water and activates an alarm at the nurses station when the water
temperature exceeds 110 degrees Fahrenheit. (A, B,)