77 Ill. Adm. Code 330.3360
Exit Facilities and Subdivision of Floor Areas
Section 330
Section 330.3360Â Exit
Facilities and Subdivision of Floor Areas
Every building shall meet the
following requirements:
a)Â Â Â Â Â Â Â Â An exit shall be a way of departure from the interior of the
building to the open air outside at the ground level. It may comprise vertical
and horizontal means of travel such as doorways, corridors, passageways,
stairways, and ramps, including all elements necessary for emergency escape
from the building. An exit begins at any doorway or other point of access to
an exit from which residents may proceed to the exterior of the building with
reasonable safety.
b)Â Â Â Â Â Â Â Â At least two exits, remote from each other, shall be provided
for each floor or fire section of the building used by residents. At least one
of the exits from each floor or fire section shall be an exit door, stairway,
or smokeproof tower. (A, B)
c)Â Â Â Â Â Â Â Â All other exits shall be either of the above type or a
horizontal or ramp type. (B)
d)Â Â Â Â Â Â Â Â Travel distance
1)Â Â Â Â Â Â Â Â Travel distance between any room door intended as exit access
and an exit shall not exceed 100 feet.
2)Â Â Â Â Â Â Â Â Travel distance between any point in a room and an exit shall
not exceed 150 feet.
3)Â Â Â Â Â Â Â Â Travel distance between any point in an institutional sleeping
room or suite and an exit access door of that room or suite shall not exceed 50
feet.
4)Â Â Â Â Â Â Â Â Minimum travel distances specified in subsections (d)(1) and
(d)(2) of this Section may be increased by 50 feet in buildings completely
equipped with automatic fire extinguishing systems. (A, B)
e)Â Â Â Â Â Â Â Â Exits shall be arranged so there are no pockets or dead-ends
exceeding 30 feet. (A, B)
f)        All main exits shall lead directly to the outside. Any
corridor or passageway a part of the exit route shall be enclosed as required
for stairways. (A, B)
g)Â Â Â Â Â Â Â Â Decorative materials applied to walls or ceilings in means of
egress and any room shall have a flame spread rating not to exceed 25 except in
individual rooms of not over four persons in capacity which may have a rating
of not more than 75. (A, B)
h)Â Â Â Â Â Â Â Â Decorative materials applied to wall or ceiling surfaces of
corridors more than 48 inches above the floor shall not ignite nor flame when
inserted for five minutes in a furnace heated to 1200 degrees Fahrenheit. (A,
B)
i)Â Â Â Â Â Â Â Â Â Floor coverings shall have a smoke developed rating not to
exceed 450 as an average of the flaming and nonflaming values as determined by
the test procedures outlined in Appendix II NBS Technical Notes 708. (A, B)
j)Â Â Â Â Â Â Â Â Â Each floor shall be divided into at least two fire sections
by a one hour fire rated smokestop partition, located to provide ample space on
each side for the total number of residents on the floor. Additional
partitions may be necessary for the safety of the residents. (A, B)
k)Â Â Â Â Â Â Â Â Openings in smokestop partition shall be protected by a pair
of approved doors with a fire resistive rating of at least three-fourths of an
hour, shall be self-closing, and shall be closed at all times unless they have
magnetic hold devices connected to the fire detection or sprinkler system. The
doors shall swing in a direction opposite from the other and shall be three
feet eight inches in clear width. (A, B)
l)Â Â Â Â Â Â Â Â Â Corridor length between smokestop partitions, horizontal
exits, or from either to the end of the corridor on any institutional sleeping
floor shall not exceed 150 feet. (A, B)
m)Â Â Â Â Â Â Â Corridor partition walls shall be continuous from the floor
slab to the underside of the floor or roof slab above, through any concealed
spaces such as those above the suspended ceilings and through interstitial
structural and mechanical spaces. (A, B)