77 Ill. Adm. Code 330.3720
Plumbing and Heating
Section 330
Section 330.3720Â Plumbing
and Heating
a)Â Â Â Â Â Â Â Â Every existing facility shall comply with the Department's rules
titled Illinois Plumbing Code.
b)Â Â Â Â Â Â Â Â All plumbing installations and fixtures on the premises shall
be of such a type and design that danger of contaminated water entering the
drinking water piping by backflow or backsiphonage is eliminated. The
following standards shall be used as a guide to determine satisfactory
compliance of individual fixtures:
1)Â Â Â Â Â Â Â Â Lavatory faucets shall discharge at least one inch above the
top rim of the lavatory bowl;
2)Â Â Â Â Â Â Â Â Faucets for bathtubs, sinks, and laundry tubs shall discharge
at least two inches above the top rim of the fixture;
3)Â Â Â Â Â Â Â Â Flush tank type toilets shall be equipped with approved
antisiphon ball cocks, installed so that the effective air opening of the
vacuum breaker is at least one inch above the top of the overflow tube in the
toilet flush tank;
4)Â Â Â Â Â Â Â Â Flushometer type toilets shall be equipped with approved
vacuum breakers installed on the discharge side of the flush valve and at least
four inches above the top of the toilet bowl;
5)Â Â Â Â Â Â Â Â Dishwashing machines, laundry machines, urinals, and drinking
fountains shall be installed so as to provide backflow protection;
6)Â Â Â Â Â Â Â Â All fixtures having, or capable of receiving, a hose shall
have a vacuum breaker located at least six inches above the highest head that
normally may be placed on the unit. The height of the antisiphon unit should
be sufficient to prevent any pressure on the unit, other than atmospheric
pressure, when the control valve is closed;
7)Â Â Â Â Â Â Â Â Hot water distribution systems shall be arranged to provide
hot water of at least 100 degrees Fahrenheit at each hot water outlet at all
times;
8)Â Â Â Â Â Â Â Â Hot water available to residents at shower, bathing and hand-washing
facilities shall not exceed 110 degrees Fahrenheit; and
9)Â Â Â Â Â Â Â Â Protective measures, including, but not limited to,
installation of a mixing valve, limited access to controls, and checking water
temperatures daily at various points, shall be implemented to ensure that the
temperature of hot water available to residents at shower, bathing and hand-washing
facilities shall not exceed 110 degrees Fahrenheit.
c)
Areas
of a nursing home used by residents of the nursing home
shall
be air
conditioned and heated by means of operable air-conditioning and heating
equipment. The areas subject to this air-conditioning and heating requirement
include, without limitation, bedrooms or common areas such as sitting rooms,
activity rooms, living rooms, community rooms, and dining rooms.
(Section
3-202(8) of the Act)
1)Â Â Â Â Â Â Â Â The
air-conditioning system shall be capable of maintaining an ambient air
temperature of between 75 degrees Fahrenheit and 80 degrees Fahrenheit,
pursuant to the requirements of Section 330.770(j).
2)Â Â Â Â Â Â Â Â The facility shall be equipped with a central heating plant
and have a radiator, convector, or register in each room used by residents or
staff.
3)Â Â Â Â Â Â Â Â The mechanical system shall be capable of maintaining a
temperature of at least 75 degrees Fahrenheit, pursuant to the requirements of
Section 330.770(j) at all times.
4)Â Â Â Â Â Â Â Â Alternative types of heating systems, such as ground water
source heat pumps, may be accepted, provided that they meet or exceed the
minimum requirements of this subsection (c).