77 Ill. Adm. Code 330.3970
Hazardous Areas and Combustible Storage
Section 330
Section 330.3970Â Hazardous
Areas and Combustible Storage
Every existing facility shall
meet the following requirements:
a)Â Â Â Â Â Â Â Â A central heating plant (including any coal storage) shall be
located in a separate room. The room, including the ceiling and any doors,
shall be constructed of, or satisfactorily protected by, approved fire
resistive material providing a fire resistance rating of at least one hour.Â
All doors to the room shall be protected with asbestos and metal on the furnace
room side (or equivalent protection), swing into the room, and be
self-closing. The rooms shall be adequately vented to the outside atmosphere
to properly support combustion in the furnace. (Alternate modern types of
heating systems are prohibited unless approved by the Department.)
b)Â Â Â Â Â Â Â Â The entire basement ceiling in non-fire resistive buildings
shall be protected with one-hour rated materials if it is not practical to
provide a separate room for the heating plant.
c)Â Â Â Â Â Â Â Â All exposed heating ducts in the basement and the smoke pipe
or breeching shall be located a safe distance from all combustible material.Â
If they are not a safe distance, the combustible material shall be properly
covered with a satisfactory resistive material.
d)Â Â Â Â Â Â Â Â All installations of fuel oil, gas, or liquefied petroleum gas
heating equipment and appliances shall conform to the following NFPA standards:
1)Â Â Â Â Â Â Â Â NFPA 31.
2)Â Â Â Â Â Â Â Â NFPA 54.
3)Â Â Â Â Â Â Â Â NFPA 58.
e)Â Â Â Â Â Â Â Â Auxiliary gas or electric space heaters of an approved closed
type may be installed in areas requiring more heat than is produced by the
central heating system. Heaters in corridors shall be ceiling hung or wall
recessed units.
f)Â Â Â Â Â Â Â Â Floor type heaters or furnaces are not permitted.
g)Â Â Â Â Â Â Â Â All paints, oils, and flammable materials shall be stored in a
fire resistive room in approved metal containers and metal cabinets, or stored
outside the building.