77 Ill. Adm. Code 350.2660
Nursing Unit
Section 350
Section 350.2660Â Nursing
Unit
a)Â Â Â Â Â Â Â Â The number of resident beds in a nursing unit shall not exceed
75 beds. Not less than 60 percent of the resident beds shall be in bedrooms
with one or two beds.
b)Â Â Â Â Â Â Â Â General Requirements for Bedrooms
1)Â Â Â Â Â Â Â Â Resident bedrooms shall have an entrance directly off a
corridor with an entrance door which swings into the room.
2)Â Â Â Â Â Â Â Â Resident bedrooms shall have adequate and satisfactory
artificial light and be equipped in accordance with Section 350.2740(d) and
(c).
3)Â Â Â Â Â Â Â Â Residents shall have access to a toilet room without entering
the general corridor area.
4)Â Â Â Â Â Â Â Â The facility shall provide a closet or wardrobe of at least
six square feet for each resident.
5)Â Â Â Â Â Â Â Â Resident bedroom floors shall be at or above grade level.
6)Â Â Â Â Â Â Â Â Each room used as a resident bedroom shall have at least one
outside window, and a total window area to the outside equal to at least
one-tenth the floor area of the room.
7)Â Â Â Â Â Â Â Â No resident bedroom shall be located more than 120 feet from
the nurses' station, clean utility room, and soiled utility room.
c)Â Â Â Â Â Â Â Â Resident Bedrooms
1)Â Â Â Â Â Â Â Â Single resident bedroom shall contain at least l00 square
feet. Multiple resident bedrooms shall contain at least 80 square feet per bed.
Minimum usable floor area shall be exclusive of toilet rooms, closets, lockers,
wardrobes, alcoves, vestibules, or clearly definable entryways.
2)Â Â Â Â Â Â Â Â Multiple resident bedrooms shall not have more than four beds
nor more than three beds deep from an outside wall. All beds shall have a
minimum clearance of three feet at the foot and sides of the bed.
d)Â Â Â Â Â Â Â Â Special Care Room
1)Â Â Â Â Â Â Â Â The facility shall provide a special care room for each 150
beds.
2)Â Â Â Â Â Â Â Â This room shall be provided with a private toilet room
containing water closet, lavatory, bathtub or shower and all other necessary
facilities to meet the resident's needs.
3)Â Â Â Â Â Â Â Â This room shall be located to allow direct visual supervision
from the nurses' station.
4)Â Â Â Â Â Â Â Â The room may be included in the authorized maximum bed
capacity for the facility. It is permissible for the room to be occupied by a
resident, not in need of special care, provided the resident is clearly
informed and understands he or she will be immediately transferred out of the
room any time of day or night, whenever the room is needed to care for a
resident requiring special care.
e)Â Â Â Â Â Â Â Â Nurses' Station
1)Â Â Â Â Â Â Â Â The facility shall provide a minimum of one station per floor
with direct access to the corridor for each nursing unit. The location of this
station shall allow visual control of each resident room served without the use
of mirrors. Separation shall be provided from the utility rooms. (B)
2)Â Â Â Â Â Â Â Â The nurses' station shall provide space for charting and
storage for administrative supplies. (B)
3)Â Â Â Â Â Â Â Â A lounge with toilet room shall be provided near each station
for nursing staff. Lockers for safekeeping of coats and personal effects may be
provided within this space or in a convenient central location. (B)
f)Â Â Â Â Â Â Â Â Bath and Toilet Rooms
1)Â Â Â Â Â Â Â Â The resident bedroom toilet room shall serve no more than two
resident rooms nor more than eight beds. The toilet room shall contain a water
closet and a lavatory. The lavatory may be omitted from the toilet room when
the resident room contains a lavatory.
2)Â Â Â Â Â Â Â Â The facility shall provide one wheelchair resident toilet room
for each sex residing in a nursing unit. The room shall be accessible from the
corridor. This room shall contain a water closet and lavatory.
3)Â Â Â Â Â Â Â Â A special wheelchair resident toilet room is not required when
all resident toilet rooms can accommodate wheelchair residents.
4)Â Â Â Â Â Â Â Â The facility shall provide one training toilet room on each
nursing floor that is accessible from the corridor. Three-foot clearance at
the front and both sides of the water closet shall be provided. This room
shall contain a lavatory accessible for wheelchair use.
5)Â Â Â Â Â Â Â Â The facility shall provide one bathtub or shower for each ten
resident beds per nursing unit which are not served by bathing or showering
facilities in resident rooms.
6)Â Â Â Â Â Â Â Â All shower stalls for residents not needing assistance shall
be at least three feet square and shall have no curb.
7)Â Â Â Â Â Â Â Â The facility shall provide at least one bathtub for assisted
bathing per nursing unit. There shall be a clear area at least three feet wide
at both sides and one end of the tub.
8)Â Â Â Â Â Â Â Â The facility shall provide at least one shower stall for
assisted showering per nursing unit. The shower stall shall be at least four
feet square with no curb.
9)Â Â Â Â Â Â Â Â Provide a toilet room with a water closet and lavatory,
accessible to the assisted bathtub and shower without entering the general
corridor. This room may be arranged to serve as the training toilet facility.
10)Â Â Â Â Â Â Â Â Grouped bathing and toilet facilities shall be partitioned or
curtained for privacy.
g)Â Â Â Â Â Â Â Â Utility Rooms
1)Â Â Â Â Â Â Â Â The clean utility room shall have direct access to a corridor,
or access may be through the nurses' station entrance. This room shall contain
work counters, single or double compartment sink with integral drainboard,
storage cabinets, and an autoclave. (Autoclave may be waived in lieu of other
methods if sterilization is approved by Department.)
2)Â Â Â Â Â Â Â Â A clean linen storage room or closet within the clean utility
room shall be provided. If a closed cart system is used, storage may be in an
alcove.
3)Â Â Â Â Â Â Â Â The soiled utility room shall have direct access to a
corridor. This room shall contain work counters, double compartment sink with
integral drainboard, storage cabinets, a clinical rim flush sink, and
sanitizer.
4)Â Â Â Â Â Â Â Â The charging room for a linen chute shall be large enough to
unload the collecting cart with the door closed.
h)Â Â Â Â Â Â Â Â A medicine station shall be provided for convenient and prompt
24 hour distribution of medicine to residents. The medicine station shall be
under the nursing staff's visual control and contain a work counter,
refrigerator, and locked storage for biologicals and drugs. A sink for
handwashing and preparation of medication shall be provided in the medicine
station.
i)Â Â Â Â Â Â Â Â Â A nourishment station shall be provided with a handwashing
sink and equipment including refrigerator, and storage cabinets for serving
nourishment between scheduled meals. Ice for residents' use shall be provided
only by icemaker dispenser units.
j)Â Â Â Â Â Â Â Â Â A room for examination and treatment of residents shall be
provided and shall have a minimum floor area of 100 square feet, excluding
space for vestibule, closets and work counters (whether fixed or movable). The
minimum room dimension shall be ten feet. The room shall contain a lavatory or
sink equipped for handwashing; a work counter; storage facilities; and a desk,
counter, or shelf space for writing.
k)Â Â Â Â Â Â Â Â Equipment storage rooms shall be provided for storage of
equipment such as I.V. stands, inhalators, air mattresses, walkers, and
wheelchairs.
l)Â Â Â Â Â Â Â Â Â Parking space for wheelchairs shall be provided and located
out of path of normal traffic.