77 Ill. Adm. Code 350.2920
Codes and Standards
Section 350
Section 350.2920Â Codes and
Standards
a)Â Â Â Â Â Â Â Â Nothing stated herein shall relieve the sponsor from
compliance with building codes, ordinances and regulations which are enforced
by city, county or other local jurisdictions. (B)
b)Â Â Â Â Â Â Â Â The 1981 Edition of the National Fire Protection Association
(NFPA) Standard No. 101, Life Safety Code for existing structures and all
appropriate references under Appendix "B" of that Code, but no
subsequently amended edition of the Code, shall apply to and become a part of
these standards. Pursuant to the Medicare-Medicaid certification requirements
of 42 CFR 442.507(c) (1983), but no subsequently amended editions of these
Federal regulations, any facility that on November 26, 1982 complied with the
requirements of the 1967 edition of the Life Safety Code, rather than the 1981
edition of the Life Safety Code, will be accepted by the Department for
licensure and certification as long as the facility continues to remain in
compliance with the 1967 edition of the Code. (A, B)
c)Â Â Â Â Â Â Â Â The following exceptions to the 1967 Life Safety Code have
been established by the Department:
1)Â Â Â Â Â Â Â Â Facilities shall be of the heights and construction types with
sprinkler requirements identified in Table C. (B)
2)Â Â Â Â Â Â Â Â Dead-end corridors greater than 50 feet in length shall be
altered so that exits are accessible in at least two directions from all points
in aisles, passageways, and corridors. (B)
3)Â Â Â Â Â Â Â Â Exit discharge doors and resident sleeping doors must be at
least 34 inches in width. Width required is the width of the door leaf.
4)Â Â Â Â Â Â Â Â All corridors shall be at least four feet wide.
d)Â Â Â Â Â Â Â Â The following equivalencies have been established by the
Department:
1)Â Â Â Â Â Â Â Â Where corridor partition walls are not continuous from the
floor slab to the underside of the floor or roof slab above, through any
concealed spaces such as those above the suspended ceilings and through
interstitial structural and mechanical spaces, the following equivalencies are
permitted:Â (B)
A)Â Â Â Â Â Â Â A membrane ceiling which may be lath and plaster or drywall or
a lay-in ceiling with all tiles clipped down and with all clips remaining in
place, or with all the tiles weighing at least one pound per square foot. The
ceiling may be suspended but it must be constructed continually from exterior
wall to exterior wall and must be part of a one hour rated assembly. All
recessed lights, all duct outlets and all speaker outlets must be properly
protected in accordance with Code. Plenums are not allowed unless each outlet
is properly protected. This concept is applicable only to two-hour fire
resistive and one-hour protected noncombustible construction.
B)Â Â Â Â Â Â Â A membrane ceiling of at least a one hour rating (such as two
layers of five-eighths inch Fire Code drywall) is acceptable for
noncombustible, one hour protected ordinary, ordinary, one hour protected wood
frame, wood frame and heavy timber construction.
C)Â Â Â Â Â Â Â Corridor walls need not run up in two-hour fire resistive and
one-hour protected noncombustible construction if automatic sprinklers are
installed throughout.
D)Â Â Â Â Â Â Â Smoke detectors may be used in lieu of continuous corridor wall
construction all building construction types which are equipped throughout with
an automatic extinguishment system required by these Standards. Automatic heat
detectors, in lieu of automatic smoke detectors, may be installed in kitchens,
laundry rooms, boiler-furnace rooms and attic spaces.
2)Â Â Â Â Â Â Â Â This equivalency is applicable only to those facilities which
are in conformance with these requirements on the date of promulgation of these
standards and only if the facility remains in conformance. The equivalency is
applicable to facilities with nonconforming construction type. The following
requirements must be met for facilities four stories or more in height of
protected ordinary construction.
A)Â Â Â Â Â Â Â The fire resistance rating of all structural members must meet
the two-hour fire resistive classification of NFPA 220, Standard Types of
Building Construction, dated May, 196l, except that floor and roof framing
members and nonbearing walls may be of combustible construction.
B)Â Â Â Â Â Â Â Smoke detectors must be installed in all resident rooms,
corridors, living areas, day rooms and in all hazardous and severely hazardous
areas throughout the facility. However, automatic heat detectors may be
installed, in lieu of automatic smoke detectors, in kitchens, laundry rooms,
boiler-furnace rooms and attic spaces (places where smoke, dust and humidity
sometimes activate smoke alarms when no fire is present, resulting in false
fire alarms), if the facility chooses to do so for the purpose of reducing the
number of false fire alarms. A zone readout identifying areas involved in a
fire must be provided.
C)Â Â Â Â Â Â Â All electrical systems shall meet the National Electrical Code
in effect at the time of acceptance of the facility.
D)Â Â Â Â Â Â Â Facility shall establish and enforce written procedures to
prohibit smoking in resident sleeping rooms and corridors. Smoking is
permitted only in controlled areas.
E)Â Â Â Â Â Â Â A complete automatic extinguishment system shall be installed
throughout the facility.
F)Â Â Â Â Â Â Â Â All health survey deficiencies must be corrected.
G)Â Â Â Â Â Â Â The physically handicapped residents shall be housed on the
lowest sleeping room floor and ambulant residents may be housed on any floor.
H)Â Â Â Â Â Â Â Complete smoke barriers including one-hour rated walls and one
and three-quarters inch thick solid core wood corridor doors with closers shall
be installed as directed by the Department.
e)        The following rules which were effective at the date of
approval by the Department of the final drawings and specifications or the
final inspection of the building apply:Â (B)
1)Â Â Â Â Â Â Â Â Illinois State Plumbing Code (77 Ill. Adm. Code 890),
Department of Public Health
2)Â Â Â Â Â Â Â Â Illinois Accessibility Code (71 I11. Adm. Code 400), Capitol
Development Board
3)Â Â Â Â Â Â Â Â Fire Prevention and Safety (41 Ill. Adm. Code 100), Office of
the State Fire Marshal
4)Â Â Â Â Â Â Â Â Food Service Sanitation (77 Ill. Adm. Code 750), Department of
Public Health
5)Â Â Â Â Â Â Â Â Boiler and Pressure Vessel Safety (41 Ill. Adm. Code 120,
Office of State Fire Marshal
f)Â Â Â Â Â Â Â Â The requirements in this Part govern in cases of differences
between this Part and the rules listed in this Section. (B)