77 Ill. Adm. Code 350.2960
Nursing Unit
Section 350
Section 350.2960Â Nursing
Unit
a)Â Â Â Â Â Â Â Â General Requirements for Bedrooms
1)Â Â Â Â Â Â Â Â Resident bedrooms shall have an entrance directly off a
corridor with an entrance door that swings into the room. Rooms used as
bedrooms and included in the licensed capacity as of December 24, 1987, which
do not open directly into corridors but instead open into large
living/dining/activity areas, are exempt from this rule. However, no additional
such rooms will be permitted to be established after December 24, 1987.
2)Â Â Â Â Â Â Â Â Resident bedroom shall have adequate and satisfactory
artificial light and be equipped in accordance with Section 350.3040(c)(2) and
(d).
3)Â Â Â Â Â Â Â Â Resident toilet rooms shall open directly into a corridor or
into a resident's bedroom. (B)
4)Â Â Â Â Â Â Â Â A closet or wardrobe at least six square feet shall be
provided for each resident.
5)Â Â Â Â Â Â Â Â Each bedroom floor shall be no more than three feet below the
adjacent ground level.
6)Â Â Â Â Â Â Â Â Each room used as a resident bedroom shall have at least one
outside window, and a total window area to the outside equal to at least
one-tenth the floor area of the room.
b)Â Â Â Â Â Â Â Â Resident Bedrooms
1)Â Â Â Â Â Â Â Â Each single resident bedroom shall contain at least 100 square
feet of usable floor area. Each multiple resident bedroom shall contain at
least 80 square feet per bed of usable floor area.  Minimum usable floor area
shall be exclusive of toilet rooms, closets, lockers, wardrobes, alcoves,
vestibules, or clearly definable entryways. Those bedrooms for which
facilities had waivers to this subsection (b)(1) on (and continuously since)
December 24, 1987, and which have at least 90 square feet for single bedrooms
and 70 square feet per bed for multi-bedrooms, are exempt from this subsection
(b)(1). Those bedrooms for which facilities had waivers to this subsection
(b)(1) on (and continuously since) December 24, 1987, but which have less than
90 square feet for single bedrooms and 70 square feet per bed or
multi-bedrooms, continue to be subject to waiver procedures on an annual basis.
(See Section 350.320.)
2)        Maximum room capacity shall be four residents. Beds shall be
at least three feet apart and no more than three deep from an outside wall.Â
There shall be a minimum of ten feet between walls or a wall and any built-in
furniture or storage space.
c)Â Â Â Â Â Â Â Â Special Care Room
1)Â Â Â Â Â Â Â Â Provide a special care room for each 150 beds.
2)Â Â Â Â Â Â Â Â Provide this room with a toilet lavatory and all other
necessary facilities to meet the resident's needs and as required to care for
an ill resident.
3)Â Â Â Â Â Â Â Â This room shall be located to provide proper and efficient
supervision of the resident by the nursing staff.
4)Â Â Â Â Â Â Â Â The room may be included in the authorized maximum bed
capacity for the facility. It is permissible for the room to be occupied by a
resident, not in need of special care, provided the resident is clearly
informed and understands he will be immediately transferred out of the room any
time of day or night, whenever the room is needed to care for a resident
requiring special care.
d)Â Â Â Â Â Â Â Â Nurses' Station
1)        Provide a minimum of one nurses' station on each floor. The
station shall have direct access to a corridor, shall be located near the area
it will serve, and shall be designed to provide visual control of the area. It
shall be separated satisfactorily from the nurses' utility rooms. In Intermediate
Care Facilities for the Developmentally Disabled one nurses' station serving
two floors housing residents is acceptable if there are less than l5 beds on an
adjacent floor which are served by the nurses' station. (B)
2)Â Â Â Â Â Â Â Â At least one nurses' station shall have a medicine sink with
hot and cold running water, a work counter, a medicine cabinet, and necessary
equipment and furnishings.
3)Â Â Â Â Â Â Â Â Provide a nurses' toilet and handwashing sink convenient to
the nurses' station.
e)Â Â Â Â Â Â Â Â Bath and Toilet Rooms
1)Â Â Â Â Â Â Â Â The maximum capacity of resident beds on each floor shall be
used to determine the number of fixtures required even though some of the beds
are not occupied.
A)Â Â Â Â Â Â Â Provide a minimum of one water closet, one lavatory, and one
bathtub or shower for each sex on each floor occupied by residents.
B)Â Â Â Â Â Â Â Provide a minimum of one lavatory and one water closet for each
ten resident beds on each floor.
C)Â Â Â Â Â Â Â Provide a minimum of one bathtub or shower for each 15 resident
beds on each floor.
D)Â Â Â Â Â Â Â Each lavatory shall be provided with a well-illuminated mirror.
2)Â Â Â Â Â Â Â Â All bath and toilet rooms shall be easily accessible, and
conveniently located. Group bath and toilet facilities shall be partitioned or
curtained for privacy.
3)Â Â Â Â Â Â Â Â All showers, other than those for residents needing assistance
in bathing, shall have minimum dimensions of three feet by three feet.
4)Â Â Â Â Â Â Â Â Shower stalls shall have a low or no curb at the entrance
opening. Under certain circumstances this may be waived but in no instances can
the curb be higher than three inches.
5)Â Â Â Â Â Â Â Â If toilet rooms provided adjacent to residents' bedrooms are
not large enough to permit use by wheelchair residents, at least one toilet
room or enclosure measuring five feet by six feet shall be provided on each
floor housing residents. Provide a lavatory usable by wheelchair residents in
this room.
6)Â Â Â Â Â Â Â Â Provide on each floor at least one bathing facility or
enclosure of not less than eight feet, six inches by eight feet, six inches
with an acceptable system for assistance in bathing persons with physical
disabilities. If a shower is installed instead of a bathtub, such shower shall
have a minimum dimension of four feet wide by three feet six inches deep.Â
These showers shall have a water inlet to which is connected a flexible hose
with spray or shower head attached to the end of the hose. If desired, a
conventional shower head installation may also be provided but it must be
valved off from the lower water inlet.