77 Ill. Adm. Code 350.3030
Plumbing Systems
Section 350
Section 350.3030Â Plumbing
Systems
a)Â Â Â Â Â Â Â Â All plumbing systems shall be designed and installed in
accordance with the requirements of the Department's rules entitled
"Illinois Plumbing Code" (77 Ill. Adm. Code 890) except that the
number of water closets, lavatories, bath tubs, showers and other fixtures
shall be as required by these Requirements and the facility program. (B)
b)Â Â Â Â Â Â Â Â Plumbing Fixtures
1)Â Â Â Â Â Â Â Â Plumbing fixtures shall be of non-absorptive acid-resistant
materials and shall be kept in good repair.
2)Â Â Â Â Â Â Â Â Clinical rim flush sinks shall have an integral trap in which
the upper portion of the trap seal provides a visible water surface.
3)Â Â Â Â Â Â Â Â When existing showers or tubs are replaced or additional
showers or tubs provided, the shower bases and tub bottoms shall be designed
with nonslip surfaces.
c)Â Â Â Â Â Â Â Â Water Supply Systems
1)Â Â Â Â Â Â Â Â Water supply systems shall be designed to supply potable water
at sufficient pressure and volume to operate all plumbing fixtures and
equipment during maximum demand periods.
2)Â Â Â Â Â Â Â Â It is recommended that each water service main, branch main,
riser and branch to a group of fixtures be valved. Stop valves should be
provided at each fixture.
3)Â Â Â Â Â Â Â Â Hot water distribution systems shall be arranged to provide
hot water of at least 100 degrees Fahrenheit at each hot water outlet at all
times.
4)Â Â Â Â Â Â Â Â Hot water available to residents at shower bathing and
handwashing facilities shall not exceed 110 degrees Fahrenheit (A,B)
5)Â Â Â Â Â Â Â Â Protective measures, such as but not limited to, installation
of a mixing valve, limited access to controls, and checking water temperatures
daily at various points, shall be implemented to insure that the temperature of
hot water available to residents at shower, bathing and handwashing facilities
shall not exceed 110 degrees Fahrenheit (A,B)
d)        Hot Water Heaters and Tanks. Water storage tanks shall be
fabricated of corrosion resistant metal or lined with non-corrosive material.
e)        Drainage Systems. Special precautions shall be taken to
protect food preparation, serving or storage areas from possible leakage or
condensation from necessary overhead piping systems. (B)
f)        Fire Extinguishment Systems. All fire extinguishment systems
shall be designed and installed in accordance with NFPA 101 and NFPA l3. All
fire extinguishment systems shall be maintained in accordance with NFPA l3A.Â
(A, B)