77 Ill. Adm. Code 350.3910
Exit Facilities and Subdivision of Floor Areas
Section 350
Section 350.3910Â Exit
Facilities and Subdivision of Floor Areas
a)Â Â Â Â Â Â Â Â At least two exits, remote from each other, shall be provided
for each floor or fire section of the building used by residents. All exits
shall be so arranged as to provide a safe path of travel to the outside of the
building without traversing any corridor or space exposed to an unprotected
vertical opening, except that traversing unprotected vertical openings may be
permitted in existing sprinklered buildings. At the upper floor level, at
least one of the required means of egress shall consist of an interior stairway
enclosed at the top and bottom, an enclosed outside stairway, or a horizontal
exit. Every sleeping room, unless it has two doors providing separate ways of
escape, or has a door opening directly to the outside of the building, shall
have at least one outside window which can be opened from the inside, without
the use of tools, to provide a clear opening of not less than 16 inches in
least dimension and 400 square inches in area, with the bottom of the opening
not more than four feet above the floor.
b)Â Â Â Â Â Â Â Â An unenclosed outside stairway may be used as one of the two
required means of egress from the second floor, only in existing buildings,
subject to the approval of the Department, as determined by an onsite
inspection. The inspector will examine the stair for structural stability,
height of risers, width of treads, width of stairway, handrails, and
maintenance, including decay or dry rot in accordance with standards found in
Section 350.3880(a) and (b).
1)Â Â Â Â Â Â Â Â Unenclosed outside stairways shall not constitute more than 50
percent of the required exit capacity, in any case. No more than one of the
exits from the second floor may be an unenclosed outside stairway. (B)
2)Â Â Â Â Â Â Â Â Fire escapes need not be of non-combustible construction.
c)Â Â Â Â Â Â Â Â Means of egress shall be so arranged that there are no dead
end pockets, hallways, corridors, passageways, or courts whose depth exceeds 20
feet. (B)
d)Â Â Â Â Â Â Â Â Corridor walls shall have a fire-resistive rating of at least
one hour. Corridor walls may terminate at the underside of the ceiling. (B)