77 Ill. Adm. Code 350.4030
New Construction Requirements
Section 350
Section 350.4030Â New
Construction Requirements
The requirements listed in
Sections 350.3780 through 350.4010 for existing facilities also apply to new
construction unless modified by this Section . This Section applies only to
new construction.
a)Â Â Â Â Â Â Â Â Single resident bedrooms shall contain at least 100 square
feet in area. Multiple resident bedrooms shall contain at least 75 square feet
per bed in area. Minimum usable floor areas do not include any space utilized
for closets, free-standing wardrobe units, bathrooms, and clearly definable
entryways.
b)Â Â Â Â Â Â Â Â Provide a closet or wardrobe of at least six square feet in
area for each resident.
c)Â Â Â Â Â Â Â Â The living, dining, and activity functions may be combined into
one room, or may be in separate rooms. However, the combined area of these
functions shall not be less than 30 square feet per resident bed.
d)Â Â Â Â Â Â Â Â Corridor doors shall be a minimum of one and three-quarters
inches thick solid core wood. Louvers in doors shall not be permitted except
as approved by the Department. (B)
e)Â Â Â Â Â Â Â Â Interior stairways must be enclosed with a minimum of one hour
rated walls and a minimum of one and three-quarters inch solid core wood doors,
with a self-closing device, at the top and bottom of the each stairway. (B)
f)Â Â Â Â Â Â Â Â In every facility all corridors used by residents shall have a
minimum unobstructed width of four feet, and shall be lighted properly at night
and at other times when necessary.
g)Â Â Â Â Â Â Â Â Facilities shall be of the heights and construction types with
sprinkler requirements identified in the Table E. (B)
h)Â Â Â Â Â Â Â Â Hazardous areas, including combustible storage, as listed in
Section 350.3930, must have walls of one hour fire resistive rating. Doors at
enclosure of hazardous areas shall be a minimum of three-fourths hour
"C" label, with automatic closer. (B)
i)Â Â Â Â Â Â Â Â Â The following additional codes are required for new
construction.
1)Â Â Â Â Â Â Â Â NFPA 13-1976 Edition, Installation of Sprinkler Systems
2)Â Â Â Â Â Â Â Â NFPA 13A-1976 Edition, Care and Maintenance of Sprinkler
Systems
3)Â Â Â Â Â Â Â Â NFPA 13D-1975 Edition, Installation of Sprinkler Systems in
One- and Two-Family Dwellings and Mobile Homes
4)Â Â Â Â Â Â Â Â NFPA 70-1978 Edition, National Electric Code (B)
j)Â Â Â Â Â Â Â Â Â Unenclosed outside stairways shall not be accepted as
constituting any part of the required means of egress for new buildings. (B)