77 Ill. Adm. Code 370.2330
Building General
Section 370
Section 370.2330Â Building
General
a)Â Â Â Â Â Â Â Â General
1)Â Â Â Â Â Â Â Â Building shall not be a structural part of a long-term care
facility or other institutional buildings.
2)Â Â Â Â Â Â Â Â Provide a room arrangement that will permit the facility to be
divided functionally into living units for not more than twenty (20)
residents. Each living unit shall contain its own living room and dining room.
3)Â Â Â Â Â Â Â Â Each facility shall have a maximum capacity of twenty (20)
beds.
4)Â Â Â Â Â Â Â Â Buildings of one (1) story in height shall be constructed of
fire resistive, protected noncombustible, protected ordinary, protected wood
frame, heavy timber, or unprotected noncombustible construction. Buildings of
fire resistive construction are not limited in height or number of stories.
Buildings of two (2) stories or more in height may be of any approved construction
type and must be equipped throughout with an approved automatic extinguishing
system, except for fire-resistive construction.
5)Â Â Â Â Â Â Â Â All corridors shall be four (4) feet in clear and unobstructed
width.
b)Â Â Â Â Â Â Â Â Doors and Windows
1)Â Â Â Â Â Â Â Â Main entrance and all exit doors shall be thirty six (36)
inches in width and shall swing outward and be provided with door closers.
2)Â Â Â Â Â Â Â Â Exit access doors and all doors used by the residents (except
toilets) shall be thirty-two (32) inches in width, side-hinged, swingingtype.
3)Â Â Â Â Â Â Â Â The doors for the toilet rooms used by residents shall have a
minimum door width of thirty (30) inches.
4)Â Â Â Â Â Â Â Â Resident toilet rooms shall open directly into a corridor or
into a resident bedroom.
5)Â Â Â Â Â Â Â Â No toilet or bathroom door shall be provided with hardware
which could allow a resident to become locked in the room. All toilet and
bathroom doors and hardware shall be designed to permit emergency ingress to
the room.
6)Â Â Â Â Â Â Â Â Locks installed on residents' bedroom and apartment suite
doors shall be so arranged that they can be quickly and easily unlocked from
the corridor side. All such locks shall be arranged to permit exit from the
room by a simple operation without the use of a key. The door may be lockable
by the occupant if the door can be locked from the corridor side and keys are
carried by the attendants at all times.
7)Â Â Â Â Â Â Â Â All doors to bedrooms and exit corridors shall be a minimum of
one and three-fourth (1¾) inches thick solid core wood or equivalent, with
positive latching, and without louvers.
8)Â Â Â Â Â Â Â Â Doors that are part of a 2-hour fire rated wall separating
sections of the building, or an abutting building, must be at least one and
one-half (1½) hour, "B" label and self-closing.
9)Â Â Â Â Â Â Â Â Doors in stairways shall have a fire protection rating of
twenty (20) minutes, be self-closing and self-latching. Provide a wire glass
vision panel in a steel frame.
10)Â Â Â Â Â Â Â Â Doors and windows shall fit snugly and be weather tight, yet
open and close easily.
11)Â Â Â Â Â Â Â Â Outside doors, other than required exits, and operable
windows shall be equipped with tight-fitting, 16-mesh screens. Screen doors
shall be equipped with self-closing devices.
c)Â Â Â Â Â Â Â Â Floors
1)Â Â Â Â Â Â Â Â Floors shall be smooth, free from cracks and finished so that
they can be easily and properly cleaned. Floors shall be covered wall to wall
with water resistant material in wet areas including but not limited to
bathrooms, kitchens, utility rooms.
2)Â Â Â Â Â Â Â Â Thresholds and expansion joints shall be flush with the floor
to facilitate use of wheelchairs and carts.
d)Â Â Â Â Â Â Â Â Walls and Ceiling
1)Â Â Â Â Â Â Â Â All rooms occupied or used by residents shall have ceilings
not less than eight (8) feet in height.
2)Â Â Â Â Â Â Â Â Corridors, storage rooms, toilet rooms and other minor rooms
shall have ceilings not less than seven (7) feet eight (8) inches in height.
3)Â Â Â Â Â Â Â Â Projections located in the path of traffic shall be not less
than six (6) feet eight (8) inches above the floor.
4)Â Â Â Â Â Â Â Â Materials used for wall construction shall be highly resistant
to impact damage.
e)Â Â Â Â Â Â Â Â Mirrors shall be installed above all lavatories except handwashing
lavatories in food preparation areas.
f)Â Â Â Â Â Â Â Â Provide paper towel dispensers and waste receptacles at all
lavatories except those located within, or directly off of a resident's room.
g)Â Â Â Â Â Â Â Â Interior finish materials (floors, walls and ceilings) shall
be either Class A (flame spread 0-25 smoke development 0-450) or Class B (flame
spread 26-75 smoke development 0-450).
h)Â Â Â Â Â Â Â Â There shall be at least one (1) approved fire extinguisher in
all basements, furnace rooms, kitchens, and laundry rooms. In addition, there
shall be at least one fire extinguisher on each floor of the building, located
so a person will not have to travel more than fifty (50) feet from any point to
reach one. They shall be inspected annually and recharged when necessary. The
date of checking and recharging shall be recorded on a tag attached to the
extinguisher.
i)
1)Â Â Â Â Â Â Â Â Approved containers with proper covers shall be provided for
storage of rubbish and waste.
2)Â Â Â Â Â Â Â Â Housekeeping throughout the building, including basements,
attics and unoccupied rooms shall be adequately performed to minimize fire
hazards.