77 Ill. Adm. Code 370.2380
Mechanical Systems
Section 370
Section 370.2380Â Mechanical
Systems
a)Â Â Â Â Â Â Â Â Mechanical systems shall be tested, balanced, and operated to
demonstrate that the installation and performance of these systems conform to
the requirements of these standards.
b)Â Â Â Â Â Â Â Â Upon the completion of the contract, the owner shall be
furnished with a complete set of manufacturer's operating and preventative
maintenance instructions, parts list with numbers and descriptions for each
piece of equipment and a copy of the air-balance report. A complete set of
these documents shall be kept on the premises.
c)Â Â Â Â Â Â Â Â The owner shall be provided with instructions in the
operational use of the systems and equipment as required.
d)        A design temperature of 75º F for both summer and winter
design conditions shall be provided for all patient use areas including corridors.
e)Â Â Â Â Â Â Â Â All ventilation supply, return and exhaust systems shall be
mechanically operated.
f)Â Â Â Â Â Â Â Â Air conditioning and ventilation systems shall be designed,
installed and maintained as required by National Fire Protection Association
Standard 90A or 90B, depending on the size of the facility.