77 Ill. Adm. Code 370.2410
Fire Alarm and Detection System
Section 370
Section 370.2410Â Fire Alarm
and Detection System
a)Â Â Â Â Â Â Â Â Provide an approved supervised fire alarm system.
b)Â Â Â Â Â Â Â Â An approved automatic smoke detection system shall be
installed on each floor level. Such system shall be installed in accordance
with National Fire Protection Association Standard 101, Section 6-3 of the 1976
Edition of the Life Safety Code, and with National Fire Protection Association
Standard 72, 1975 Edition. In no case shall smoke detectors be spaced further
apart than thirty (30) feet on center, or more than fifteen (15) feet from any
wall. The automatic smoke detection system shall be electrically interconnected
to the fire alarm system.
c)Â Â Â Â Â Â Â Â The fire alarm system shall automatically transmit the alarm
to any available municipal fire department by direct private line or through
any approved central station.