77 Ill. Adm. Code 370.2730
Building General
Section 370
Section 370.2730Â Building
General
a)Â Â Â Â Â Â Â Â General
1)Â Â Â Â Â Â Â Â Building shall not be a structural part of a long-term care
facility or other institutional buildings.
2)Â Â Â Â Â Â Â Â Provide a room arrangement that will permit the facility to be
divided functionally into living units for not more than twenty (20)
residents. Each living unit shall contain its own living room and dining room.
3)Â Â Â Â Â Â Â Â Each facility shall have a maximum capacity of twenty (20)
beds, except as provided for in Section 18 of the Community Living Facilities
Licensing Act (Ill. Rev. Stat. 1981 ch. 111½ par. 4197 et seq.) approved
September 23, 1981, as amended by Public Act 82-745.
4)Â Â Â Â Â Â Â Â Buildings of one (1) story in height shall be constructed of
fire resistive, protected noncombustible, protected ordinary, protected wood
frame, heavy timber, or unprotected noncombustible construction. Buildings of
fire resistive construction are not limited in height or number of stories.
Buildings of two (2) stories or more in height may be of any approvable
construction type and must be equipped throughout with an approved automatic
extinguishing system, except for fire-resistive construction.
5)Â Â Â Â Â Â Â Â All corridors shall be three (3) feet in clear and
unobstructed width.
b)Â Â Â Â Â Â Â Â Doors and Windows
1)Â Â Â Â Â Â Â Â Main entrance and exit doors shall be thirty-six (36) inches
in width and shall swing outward and be provided with door closers.
2)Â Â Â Â Â Â Â Â Exit access doors and all doors used by the residents (except
toilets) shall be thirty-two (32) inches in width, side-hinged, swinging type.
3)Â Â Â Â Â Â Â Â The doors for the toilet rooms used by residents shall have a
minimum door width of thirty (30) inches.
4)Â Â Â Â Â Â Â Â Resident toilet rooms shall open directly into a corridor or
into a resident's bedroom.
5)Â Â Â Â Â Â Â Â No toilet or bathroom door shall be provided with hardware
which could allow a resident to become locked in the room. All toilet and
bathroom doors and hardware shall be designed to permit emergency ingress to
the room.
6)Â Â Â Â Â Â Â Â Locks installed on resident bedroom and apartment suite doors
shall be so arranged that they can be quickly and easily unlocked from the
corridor side. All such locks shall be arranged to permit exit from the room
by a simple operation without the use of a key. The door may be lockable by
the occupant if the door can be unlocked from the corridor side and the keys
are carried by the attendants at all times.
7)Â Â Â Â Â Â Â Â All doors to bedrooms and exit corridors shall be at least one
and three-eights (1 3/8) inches thick solid core wood or equivalent, with
positive latching, and without louvers.
8)Â Â Â Â Â Â Â Â Doors that are part of a 2 hour rated fire wall separating
sections of a building, or an abutting building, must be at least one and one
half (1½) hour, 'B' label and self-closing.
9)Â Â Â Â Â Â Â Â Doors in stairways shall be at least one and three-eights
(1⅜) inches thick solid core wood or equivalent with a wire glass vision
panel in a steel frame. The door shall be self-closing and self-latching.
10)Â Â Â Â Â Â Â Â Doors and windows shall fit snugly and be weather tight, and
shall open and close easily.
11)Â Â Â Â Â Â Â Â Outside doors, other than required exits, and operable
windows shall be equipped with tight-fitting, l6-mesh screens. Screen doors
shall be equipped with self-closing devices.
c)Â Â Â Â Â Â Â Â Floors
1)Â Â Â Â Â Â Â Â Floors shall be smooth, free from cracks and finished so that
they can be easily and properly cleaned.
2)Â Â Â Â Â Â Â Â Floors in bathrooms, kitchens, and utility rooms shall be
completely covered with water resistant material.
d)Â Â Â Â Â Â Â Â Walls and Ceilings
1)Â Â Â Â Â Â Â Â All rooms occupied or used by residents shall have ceilings
not less than seven (7) feet eight (8) inches in height.
2)Â Â Â Â Â Â Â Â Corridors, storage rooms, toilet rooms and other minor rooms
shall have ceilings not less than seven (7) feet six (6) inches in height.
3)Â Â Â Â Â Â Â Â Projections located in the path of traffic shall be not less
than six (6) feet eight (8) inches above the floor.
4)Â Â Â Â Â Â Â Â Materials used for wall construction shall be highly resistant
to impact damage.
e)Â Â Â Â Â Â Â Â Mirrors shall be installed above all lavatories except
handwashing lavatories in food preparation areas.
f)Â Â Â Â Â Â Â Â Paper towel dispensers and waste receptacles shall be provided
at all lavatories, except those located within, or directly off of a resident's
room.
g)Â Â Â Â Â Â Â Â Interior finish materials (floors, walls and ceilings) shall
be either:
1)        Class A – (Flame spread 0-25 Smoke development 0-450)
2)        Class B – (Flame spread 26-75 Smoke development 0-450)
h)Â Â Â Â Â Â Â Â There shall be at least one (1) approved fire extinguisher in
all basements, furnace rooms, kitchens, and laundry rooms. In addition, there
shall be at least one fire extinguisher on each floor of the building, located
so a person will not have to travel more than fifty (50) feet from any point to
reach one. They shall be inspected annually and recharged when necessary. The
date of checking and recharging shall be recorded on a tag attached to the
extinguisher.
i)Â Â Â Â Â Â Â Â Â Approved containers with proper covers shall be provided for
storage of rubbish and waste.
j)Â Â Â Â Â Â Â Â Â Housekeeping throughout the building, including basements,
attics, and unoccupied rooms shall be adequately performed to minimize all fire
hazards.