77 Ill. Adm. Code 380.670
Physical Plant and Environmental Requirements
Section 380.670 Â Physical Plant and Environmental
Requirements
a)Â Â Â Â Â Â Â Â Consumer
living areas shall be planned and arranged with an awareness of the prevalence
of trauma in people with mental health and substance abuse issues.Â
Evidence-based practices of trauma-informed care shall be adhered to in
residential settings.
b)Â Â Â Â Â Â Â Â Private
meeting space shall be available in each facility for consumers to meet with
outside service providers, assessors, family or other persons for other
professional purposes in accordance with the consumer's treatment plan.
c)Â Â Â Â Â Â Â Â Physical
Plant Requirements. The facility shall comply with locally adopted building
codes as enforced by local authorities and Chapter 33 of NFPA 101 (see Section
380.110 (a)(1)) and any local fire codes that are more stringent than the NFPA
as enforced by local authorities or the Office of the State Fire Marshal. New
construction shall comply with Chapter 32 of NFPA 101 (see Section
380.110(a)(1)). The facility shall make available to the Department, upon
request, the report of an inspection that has been made by the local
authorities or the Office of the State Fire Marshal. The facility shall comply
with the following additional NFPA standards:
1)Â Â Â Â Â Â Â Â No.
10: Standard for Portable Fire Extinguishers
2)Â Â Â Â Â Â Â Â No.
13: Standard for the Installation of Sprinkler Systems
3)Â Â Â Â Â Â Â Â No.
25: Standard for the Inspection, Testing and Maintenance of Water-Based Fire
Protection Systems
4)Â Â Â Â Â Â Â Â No.
54: National Fuel Gas Code
5)Â Â Â Â Â Â Â Â No.
70: National Electrical Code
6)Â Â Â Â Â Â Â Â No.
72: National Fire Alarm and Signaling Code
7)Â Â Â Â Â Â Â Â No.
80: Standard for Fire Doors and Other Opening Protectives
8)Â Â Â Â Â Â Â Â No.
90A: Standard for Installation of Air Conditioning and Ventilating Systems
9)Â Â Â Â Â Â Â Â No.
96: Standard for Ventilation Control and Fire Protection of Commercial Cooking
Operations
10)Â Â Â Â Â Â Â Â No.
99: Health Care Facilities Code
11)Â Â Â Â Â Â Â Â No.
110: Standard for Emergency and Standby Power Systems
12)Â Â Â Â Â Â Â Â No.
220: Standard on Types of Building Construction
13)Â Â Â Â Â Â Â Â No.
241: Standard for Safeguarding Construction, Alteration and Demolition
d)Â Â Â Â Â Â Â Â Living
arrangements shall meet the following additional requirements:
1)Â Â Â Â Â Â Â Â A
triage center shall provide a secure room within the facility, near the
facility entrance, for the assessment of incoming consumers. The triage center
shall provide the following:
A)Â Â Â Â Â Â Â A
staff member, available as needed at the entrance of the triage center;
B)Â Â Â Â Â Â Â A
centrally located nurse duty area that gives staff a direct line of site to the
consumer, permitting constant observation;
C)Â Â Â Â Â Â Â A
window to the outside that is secured from opening and contains glazing so
that, when broken, it will not produce shards of glass that can inflict injury
to the consumer or to staff;
D)Â Â Â Â Â Â Â Features
such as electrical outlets, sprinkler heads, doorknobs, light switches, etc.,
which shall be of a type that prevent a consumer from injuring himself or
herself, accidentally or deliberately;
E)Â Â Â Â Â Â Â Adequate
space and furnishings to permit staff to assess and diagnose consumers who
present for triage;
F)Â Â Â Â Â Â Â Â Separate
restroom facilities for men and women, complete with baths or showers and
hygiene supplies, including soap, shampoo and deodorant for consumers;
G)Â Â Â Â Â Â Â A
maximum of eight individual areas for interviews and assessment. The physical
arrangement of the rooms shall preserve the safety and privacy of each consumer
served;
H)Â Â Â Â Â Â Â Laundry
services for consumer use, including laundry detergent;
I)Â Â Â Â Â Â Â Â Clean
replacement clothing for both male and female consumers, if needed by the
consumer;
J)Â Â Â Â Â Â Â Â Kitchen
equipment to provide hot meals and snacks for consumers; and
K)Â Â Â Â Â Â Â A
toilet room that is accessible from within the triage center. The toilet room
shall be equipped with a water closet and lavatory. The door to the toilet
room shall be lockable from the outside only.
2)Â Â Â Â Â Â Â Â A crisis
stabilization unit shall be a separate unit within the facility, if the
facility provides more than one level of service. In addition, a crisis
stabilization unit shall provide the following:
A)Â Â Â Â Â Â Â Meeting
and therapy rooms that comply with the level of service. The rooms shall be of
adequate size and number to accommodate the maximum consumer population of the
unit and shall be furnished for the purpose intended;
B)Â Â Â Â Â Â Â A
maximum of 16 beds;
C)Â Â Â Â Â Â Â Visual
monitoring of consumers for safety reasons, when indicated in the consumer's
treatment plan;
D)Â Â Â Â Â Â Â As
much privacy for each consumer as is clinically appropriate.
E)Â Â Â Â Â Â Â Hallways
and common areas that are visible from the nurse duty area. If electronic
monitoring devices are used, the video recording must be kept for seven days;
and
F)Â Â Â Â Â Â Â Â Features
including, but not limited to, electrical outlets, sprinkler heads, doorknobs,
and light switches that prevent a consumer from injuring himself or herself
accidentally or deliberately.
3)Â Â Â Â Â Â Â Â RRS
units shall provide the following:
A)Â Â Â Â Â Â Â Meeting
and therapy rooms in accordance with the level of service. The rooms shall be
of adequate size and number to accommodate the maximum consumer population, and
shall be furnished for the purpose intended;
B)Â Â Â Â Â Â Â Bedroom
doors that are visible from the nurse duty area;
C)Â Â Â Â Â Â Â Adequate
common space for programming; and
D)Â Â Â Â Â Â Â Sufficient
private space for consumers to meet with assessors, transition staff, and
visitors.
4)Â Â Â Â Â Â Â Â RSS
unit maybe designated as all-male or all-female, for consumers who prefer
segregated living arrangements, or for treatment purposes.
5)Â Â Â Â Â Â Â Â Transitional
Living Units shall provide the following:
A)Â Â Â Â Â Â Â Meeting
and therapy rooms according to the level of service. The rooms shall be of adequate
size and number to accommodate the maximum consumer population and shall be
furnished for the purpose intended;
B)Â Â Â Â Â Â Â Bedroom
doors that are visible from the nurse duty area; and
C)Â Â Â Â Â Â Â A
distinct unit within a facility.
6)Â Â Â Â Â Â Â Â Nurse
Duty Area
A)Â Â Â Â Â Â Â The nurse
duty area shall be either a centralized cluster serving more than one level of
service in a facility or shall be used as a supportive area within a
self-contained level of service.
B)Â Â Â Â Â Â Â The
nurse duty area shall have adequate work counters, storage areas and
communication equipment.
C)Â Â Â Â Â Â Â A
hand-washing station convenient to the nurse duty area shall be provided.
D)Â Â Â Â Â Â Â A
lounge and toilet rooms for staff shall be provided.
E)Â Â Â Â Â Â Â Closets
or compartments shall be provided for the safekeeping of coats and personal
effects of nursing personnel.
F)Â Â Â Â Â Â Â Â Charting
facilities shall be provided for nurses and doctors, including work counter and
secured file storage.
G)Â Â Â Â Â Â Â At
least one tub or shower shall be provided for each 15 beds
that do not have bathing facilities within the
consumer's room. Each tub or shower shall be in an individual room that
provides space for the private use of the bathing fixture and for drying and
dressing.
H)Â Â Â Â Â Â Â A
nourishment station with a sink equipped for hand washing, refrigerator,
storage cabinets, ice dispensing equipment, and other equipment/supplies as
necessary for serving nourishment between meals shall be provided.
I)Â Â Â Â Â Â Â Â A
clean utility/work room shall be provided in each nursing area. The clean
utility/work room shall contain a work counter, hand- washing sink and
storage. A separate designated area shall be provided for clean linen
storage. If a cart system is used, an alcove for storage of the cart may be
used.
J)Â Â Â Â Â Â Â Â A
soiled utility/workroom shall be provided and shall contain a hand-washing sink
and a waste receptacle.
K)Â Â Â Â Â Â Â A
locked janitor's closet shall be provided for each nurse duty area. The closet
shall be for the exclusive use of housekeeping staff and shall be equipped with
a floor receptor or service sink and adequate storage space for housekeeping
equipment and supplies.
L)Â Â Â Â Â Â Â Mops
and other cleaning supplies used and stored in the nurse areas shall not be
used or stored in the kitchen area.
7)Â Â Â Â Â Â Â Â The
facility shall have a smoke detection system that complies with the Smoke Detector
Act.
8)Â Â Â Â Â Â Â Â Bathrooms
shall be located and equipped to facilitate independence. When needed by the
consumer, special assistive devices shall be provided. Bathing and toilet
facilities shall provide privacy.
9)Â Â Â Â Â Â Â Â Each
single individual bedroom shall have at least 75 square feet of net floor area,
not including space for closets, bathrooms and clearly definable entryway
areas.
A)Â Â Â Â Â Â Â Each
multiple bedroom shall have at least 55 square feet of net floor area per
consumer, not including space for closets, bathrooms and clearly definable
entryway areas. A minimum of 3 feet of clearance at the foot and sides of each
bed shall be provided.
B)Â Â Â Â Â Â Â Each
bedroom within crisis stabilization units, recovery and rehabilitation supports
units, and transitional living units shall accommodate no more than two
consumers, with 5% of the rooms in the first 18 months, and 10% of the rooms in
the first three years, reserved for single occupancy.
C)Â Â Â Â Â Â Â Reasonable
storage space for clothing and other personal belongings shall be provided for
each consumer.
D)Â Â Â Â Â Â Â Each
bedroom shall have walls that extend from floor to ceiling, a fire-graded bed
that is suitable to the size of the consumer and that provides support and
comfort, if beds are provided by the agency, and at least one outside window.Â
The total window area to the outside shall be at least one-tenth of the floor
area of the room.
E)Â Â Â Â Â Â Â Each
toilet room shall be equipped with a water closet, a lavatory and a shower or
shower/tub combination.
10)Â Â Â Â Â Â Â Â The
facility shall ensure that living arrangements are free from vermin. Waste and
garbage shall be stored, transferred and disposed of in a manner that does not
permit the transmission of diseases. Water systems shall comply with the
Drinking Water Systems Code, and the facility shall maintain copies of
inspections performed by local and State inspectors in regard to health,
sanitation and environment.
e)Â Â Â Â Â Â Â Â Plumbing,
drainage facilities, and drinking water shall be maintained in compliance with
the Illinois Plumbing Code.
1)Â Â Â Â Â Â Â Â Each
facility shall be served by water from a municipal public water supply when
available.
A)Â Â Â Â Â Â Â When a
municipal public water supply is not available, the water supply shall comply
with the Drinking Water Systems Code.
B)Â Â Â Â Â Â Â If
water is supplied by a well that is not part of a municipal system, the well
shall be constructed and maintained in accordance with the Water Well
Construction Code and Illinois Water Well Pump Installation Code.
C)Â Â Â Â Â Â Â Each
facility shall have a written agreement with a water company, dairy or other
water purveyor to provide an emergency supply of potable water for drinking and
culinary purposes.
2)Â Â Â Â Â Â Â Â Hot
water temperature controls shall be maintained and regulated to prevent
scalding, so that the temperature of hot water delivered to the plumbing
fixtures that are used by consumers not exceed 115 degrees Farenheit.
3)Â Â Â Â Â Â Â Â Minimum
hot water temperature shall be maintained at the final rinse section of
dishwashing facilities as required by the Food Service Sanitation Code.
4)Â Â Â Â Â Â Â Â Suicide-resistant
grab bars (for crisis stabilization and triage centers) and other bathroom
fixtures shall be maintained at each community toilet, lavatory, shower and
bathtub used by consumers and as needed in individual consumer rooms.
5)Â Â Â Â Â Â Â Â Toilet,
hand-washing and bathing facilities shall be maintained in operating condition
and in the number and types specified in construction requirements in effect at
the time the building or unit was constructed.
6)Â Â Â Â Â Â Â Â If
the facility accepts physically handicapped consumers, bathing and toileting
appliances in the water closets shall be equipped for use by consumers with
physical handicaps. All handicapped accessible facilities shall meet the
minimum requirements of the Illinois Accessibility Code and the Americans With
Disabilities Act.
f)Â Â Â Â Â Â Â Â All
rooms, attics, basements, passageways and other spaces shall be provided with
artificial illumination in accordance with the National Electrical Code.
1)Â Â Â Â Â Â Â Â All
consumer rooms and accessible areas of corridors, storerooms, stairways, ramps,
exits and entrances shall have lighting for ease of reading, working and
passage.
2)Â Â Â Â Â Â Â Â The
facility shall provide and maintain an emergency electrical system in safe
operating condition.
g)Â Â Â Â Â Â Â Â Heating,
air conditioning and ventilating systems shall be maintained in normal
operating condition to provide a comfortable temperature and shall meet the
requirements of the American Society of Heating, Refrigerating, and Air
Conditioning Engineers Handbook of Fundamental Principles and Handbook of
Applications.
1)Â Â Â Â Â Â Â Â The
mechanical system shall be capable of maintaining a temperature of at least 75
degrees Fahrenheit.
2)Â Â Â Â Â Â Â Â The
air-conditioning system shall be capable of maintaining an ambient air
temperature of between 75 degrees Fahrenheit and 80 degrees Fahrenheit.
h)Â Â Â Â Â Â Â Â The
facility shall develop a written record of the maintenance history of the
heating, air conditioning and ventilation systems, which shall be available for
inspection by the Department.
1)Â Â Â Â Â Â Â Â A log
shall be used to document all maintenance work performed.
2)Â Â Â Â Â Â Â Â When
maintenance is performed by an equipment service company, the facility shall request
a certification that the required work has been performed in accordance with
acceptable standards. The certification shall be retained on file in the
facility for review by the Department.
i)Â Â Â Â Â Â Â Â Â The
facility shall have housekeeping procedures to routinely clean articles and
surfaces such as furniture, floors, walls, ceilings, supply and exhaust grills
and lighting fixtures.
j)Â Â Â Â Â Â Â Â Â Schedules
shall be posted and implemented that indicate areas of the facility that shall
be cleaned daily, weekly or monthly.
1)Â Â Â Â Â Â Â Â Cleaning
supplies and equipment shall be available to housekeeping staff and shall meet
the following requirements:
A)Â Â Â Â Â Â Â Cleaning
supplies and equipment shall be stored in rooms for housekeeping use only;
B)Â Â Â Â Â Â Â Appropriate
cleaning agents shall be used for all cleaning;
C)Â Â Â Â Â Â Â Mop
heads shall be removable and changed at least daily; and
D)Â Â Â Â Â Â Â Cleaning
supplies and equipment shall be kept in a secured location/area that is
accessed by authorized personnel only.
2)Â Â Â Â Â Â Â Â Housekeeping
personnel shall be employed to maintain the interior of the facility in a safe,
clean, orderly and attractive manner free from offensive odors.
3)Â Â Â Â Â Â Â Â Janitor
closets, service sinks and storage areas shall be clean and maintained to meet
the needs of the facility.
k)Â Â Â Â Â Â Â Â If
the facility operates a laundry that is separate from consumer-operated washers
and dryers for clothes, the facility laundry area shall be located in
relationship to other areas so that steam, odors, lint and objectionable noises
do not reach consumer areas.
1)Â Â Â Â Â Â Â Â The
facility laundry area shall be adequate in size, well lighted, ventilated to
meet the needs of the facility, and kept clean and sanitary.
2)Â Â Â Â Â Â Â Â Laundry
equipment shall be kept in good condition, be maintained in a sanitary
condition, and have suitable capacity.
3)Â Â Â Â Â Â Â Â Laundry
areas shall have, at a minimum, the following:
A)Â Â Â Â Â Â Â Separate
rooms for the storage of clean linen and soiled linen;
B)Â Â Â Â Â Â Â Hand-washing
facilities maintained at locations convenient for laundry personnel; and
C)Â Â Â Â Â Â Â Linen
carts labeled "soiled" or "clean" and constructed of
washable materials that shall be laundered or suitably cleaned as needed to
maintain sanitation.
4)Â Â Â Â Â Â Â Â The
facility shall implement written procedures for handling, storing, transporting
and processing linens. The written procedures shall be posted in the laundry.
5)Â Â Â Â Â Â Â Â If
the facility does not maintain a laundry service, the facility shall contract
only with a commercial laundry that meets the requirements of this Section.
l)Â Â Â Â Â Â Â Â Â The
facility, including the grounds, shall be maintained in a clean and sanitary
condition and in good condition at all times to ensure the safety and
well-being of consumers, staff and visitors.
1)Â Â Â Â Â Â Â Â Buildings
and grounds shall be free of environmental pollutants and nuisances that may
adversely affect the health or welfare of consumers to the extent that is
within the reasonable control of the facility.
2)Â Â Â Â Â Â Â Â All
buildings, fixtures, equipment and spaces shall be maintained in operable
condition.
3)Â Â Â Â Â Â Â Â Personnel
shall be employed to provide preventive maintenance and to carry out the
required maintenance program.
4)Â Â Â Â Â Â Â Â Equipment
shall meet all applicable Occupational Safety and Health Act requirements in
effect at the time of purchase. All portable electrical medical equipment
designed for 110-120 volts, 60 hertz current, shall be equipped with a
3-wire-grounded power cord with a hospital-grade 3‑prong plug. The cord
shall be an integral part of the plug.
5)Â Â Â Â Â Â Â Â The
facility shall be maintained free from vermin and rodents through operation of
a pest control program. The pest control program shall be conducted in the
main consumer buildings, all outbuildings on the property and all grounds.
m)Â Â Â Â Â Â Â The
facility shall be responsible for the regular inspection, cleaning or
replacement of all filters installed in heating, air conditioning and
ventilating systems, as necessary to maintain the systems in normal operating
conditions.
1)Â Â Â Â Â Â Â Â A
written record of inspection, cleaning or replacement shall be maintained and
available for inspection by the Department.
2)Â Â Â Â Â Â Â Â When
filter maintenance is performed by an equipment service company, the facility
shall request a certification that the filter has been inspected, cleaned or
replaced, with dates noted.
n)Â Â Â Â Â Â Â Â Emergency
Electrical Requirements
1)Â Â Â Â Â Â Â Â To
provide electricity during an interruption of the normal electric supply, an
emergency source of electricity shall be provided and connected to certain
circuits for lighting and power.
2)Â Â Â Â Â Â Â Â The
source of this emergency electrical service shall be one of the following:
A)Â Â Â Â Â Â Â A Type
3 Essential Electrical System, in accordance with NFPA 99, when the normal
service is supplied by only one central station transmission line; or
B)Â Â Â Â Â Â Â Automatic
battery-operated systems or equipment that will be effective for 90 minutes
and will be capable of supplying power for
lighting for exit signs, exit corridors, stairways, nurses' areas, the communication
system, and all alarm systems.
3)Â Â Â Â Â Â Â Â The
facility shall provide emergency electrical service for:
A)Â Â Â Â Â Â Â Illumination
of a means of egress as necessary for corridors, passageways, stairways,
landings and exit doors and all ways of approach to and through exits,
including outside lights;
B)Â Â Â Â Â Â Â Exit
signs and exit directional signs;
C)Â Â Â Â Â Â Â Fire
alarm systems and detection systems;
D)Â Â Â Â Â Â Â Communication
systems that are used for issuing instructions; and
E)Â Â Â Â Â Â Â Task
illumination in the nurse duty area.
o)Â Â Â Â Â Â Â Â Kitchen
1)Â Â Â Â Â Â Â Â Floor
material in kitchens shall be easily cleanable and shall have wear resistance
that is appropriate for the location involved, and shall be water resistant and
greaseproof. The kitchen wall base shall be tightly sealed to the wall and
floor and shall be constructed without voids or gaps that can accumulate dirt
and grime and harbor vermin. Ceiling finishes shall be smooth, sanitary and
washable, and shall be able to withstand treatment with harsh chemicals. The
ceiling finish shall be capable of being thoroughly cleaned, including any
concealed spaces that may be present.
2)Â Â Â Â Â Â Â Â Mops
and all other cleaning supplies that are used in the kitchen shall not be used
or stored anywhere else in the facility. A janitor's closet, equipped with a
floor receptor or service sink and adequate storage space for housekeeping
equipment and supplies, shall be provided for the kitchen.
3)Â Â Â Â Â Â Â Â Equipment
and furnishing installations must meet all the requirements of the following:
A)Â Â Â Â Â Â Â NFPA
56 National Fuel Gas Code;
B)Â Â Â Â Â Â Â NFPA 70 National
Electrical Code; and
C)Â Â Â Â Â Â Â NFPA
96 Standard for Ventilation Control and Fire Protection of Commercial Cooking
Operations.