77 Ill. Adm. Code 518.2160
Submission of Architectural Plans
Section 518
Section 518.2160Â Submission
of Architectural Plans
a)Â Â Â Â Â Â Â Â New Construction, Addition, or Major Alteration
1)Â Â Â Â Â Â Â Â When construction is contemplated, either for new buildings or
additions or alterations to existing buildings coming within the scope of this
Part, design development drawings and outline specifications shall be submitted
to the Department for review. Approval of design development drawings and
specifications shall be obtained from the Department prior to starting final
working drawings and specifications. The Department will provide comments or
approval within 30 working days after receipt of the drawings and
specifications and the submission being deemed complete.
2)Â Â Â Â Â Â Â Â Final Drawings
A)Â Â Â Â Â Â Â The final working drawings and specifications shall be
submitted to the Department for review and approval prior to beginning of
construction. For final approval to remain valid, contracts shall be signed
within one year after the approval date. Alternate methods of design
development and construction may be acceptable subject to the approval of the
Department. The Department will provide comments or approval within 30 working days
after receipt of the final drawings and the submission being deemed complete.
B)Â Â Â Â Â Â Â The Department shall be notified upon the award of construction
contracts.
3)Â Â Â Â Â Â Â Â Any contract modifications that affect or change the function,
design, or purpose of a facility shall be submitted to the Department for
approval prior to authorizing the modifications. The Department will provide
comments or approval within 60 working days after receipt of the drawings and
specifications.
4)Â Â Â Â Â Â Â Â Upon 90% of completion, the pre-occupancy certification
package shall be submitted to the Department.
5)Â Â Â Â Â Â Â Â As-built drawings shall be maintained by the freestanding
emergency center.
b)Â Â Â Â Â Â Â Â Minor Alterations and Remodeling. Minor alterations or
remodeling changes that do not affect the structural integrity of the building,
that do not change functional operation, that do not affect fire safety, and
that do not increase capacity over that for which the FEC is licensed need not
be submitted for approval.
c)Â Â Â Â Â Â Â Â Alterations of Water Supply, Plumbing and Drainage. No system
of water supply, plumbing, sewage, garbage or refuse disposal shall be
installed, nor any such existing system materially altered or extended, until
complete plans and specifications for the installation, alteration or extension
have been submitted to the Department and have been reviewed and approved.
d)Â Â Â Â Â Â Â Â Codes and Standards
1)Â Â Â Â Â Â Â Â Nothing stated in this Part shall relieve the licensee from
compliance with building codes, ordinances and regulations that are enforced by
city, county or local jurisdictions.
2)Â Â Â Â Â Â Â Â The recommendations of the International Building Code shall
apply insofar as those recommendations are not in conflict with the standards
set forth in this Part or with NFPA 101.
A)Â Â Â Â Â Â Â The portions of the International Building Code requiring smoke
detectors in all patient rooms and automatic door closers on all patient room
doors are hereby specifically excluded from these requirements.
B)Â Â Â Â Â Â Â The International Building Code is intended as a model code for
municipalities with no building code of their own.
C)Â Â Â Â Â Â Â NFPA 101-A shall apply only if the Department determines that
the proposed equivalent system is safe and does not constitute a hazard to the
life and safety of the staff and patients.