77 Ill. Adm. Code 518.2230
Electrical Requirements
Section 518
Section 518.2230Â Electrical
Requirements
a)Â Â Â Â Â Â Â Â General Requirements
1)Â Â Â Â Â Â Â Â All materials including equipment, conductors, controls, and
signaling devices shall be installed in compliance with applicable sections of
the NFPA 70, including Article 517, and as necessary to provide a complete
electrical system.
2)Â Â Â Â Â Â Â Â All electrical installations, including alarm, nurses' call
and communication systems, shall be tested to demonstrate that the equipment
installation and operation conforms to this Part.
b)Â Â Â Â Â Â Â Â Switchboards and Power Panels
These items
shall comply with NFPA 70. The main switchboard shall be located in an area
separate from plumbing and mechanical equipment and be accessible only to
authorized persons.
c)        Panelboards. Panelboards serving lighting and appliance
circuits shall be located on the same floor as the circuits they serve. This
requirement does not apply to the life safety system.
d)Â Â Â Â Â Â Â Â Lighting
1)Â Â Â Â Â Â Â Â All spaces occupied by people, machinery, and equipment within
buildings, approaches to and through exits from buildings, and parking lots
shall have lighting.
2)Â Â Â Â Â Â Â Â Treatment rooms shall have general lighting in addition to
local lighting provided by special lighting units at the treatment tables. The
general lighting shall provide a minimum of 100 footcandles at the treatment
tables. Each fixed special lighting unit at the tables shall be connected to
an independent circuit.
e)Â Â Â Â Â Â Â Â Receptacles (Convenience Outlets)
1)Â Â Â Â Â Â Â Â Each treatment room shall have at least two receptacles
installed on each wall or eight receptacles in diversified locations per room.
2)Â Â Â Â Â Â Â Â Each observation/treatment room shall have duplex grounding
type receptacles as specified in Article 517-18 and Article 517-19 of NFPA 70.Â
The mounting height of these receptacles shall be 22 to 42 inches above the
finished floor.
3)Â Â Â Â Â Â Â Â Duplex receptacles for general use shall be installed
approximately 50'0" apart in all corridors and within 25'0" of the
ends of corridors. These receptacles shall be circuited to the emergency
system.
f)Â Â Â Â Â Â Â Â At least two x-ray film illuminators shall be installed in
each treatment room and in the x-ray viewing room of the radiology department.
More than two units shall be installed as needed.
g)Â Â Â Â Â Â Â Â Nurses' Calling System
1)Â Â Â Â Â Â Â Â Each observation/treatment room shall be served by at least
one calling station. Calls shall register with nursing staff and shall
activate a visible signal in the corridor at the observation/treatment room
door. In multicorridor nursing units, additional visible signals shall be
installed at corridor intersections. In rooms containing two or more calling
stations, indicating lights shall be provided at each station. Nurses' calling
systems that provide two-way voice communications shall be equipped with an
indicating light at each calling station, which will remain lighted as long as
the voice circuit is operating.
2)Â Â Â Â Â Â Â Â Nurse call duty stations shall be installed in the clean work
room, soiled work room, medicine preparation room, nourishment station and
nurses' lounge of the unit.
3)Â Â Â Â Â Â Â Â A nurses' call emergency station shall be provided for
patients' use at each patient's toilet and at the shower. These stations are
to be the pull-cord type with the cord reaching within 6 inches of the floor.Â
The cords are to be located within reach of a patient.
4)Â Â Â Â Â Â Â Â In areas where patients are under constant surveillance, the
nurses' calling system may be limited to a bedside station that will actuate a
signal that can be readily seen by the other nurses.
5)Â Â Â Â Â Â Â Â A communications system that may be used by nurses to summon
assistance shall be provided in each treatment room.
h)Â Â Â Â Â Â Â Â Communication System
1)Â Â Â Â Â Â Â Â A loud speaker-type sound system shall be provided throughout
the facility to allow for announcements, such as paging of personnel and other
necessary audio functions.
2)Â Â Â Â Â Â Â Â Speakers shall be located in all areas to allow personnel to
adequately hear all audio outputs from the system.
3)Â Â Â Â Â Â Â Â The system shall be used as the communication link for
emergency announcements, i.e., code blue, impending disasters and others. The
audio line at the last speaker in the audio circuits shall be electrically
supervised against opens and grounds. The supervision shall be indicated at a
building location that is staffed 24 hours a day.
i)Â Â Â Â Â Â Â Â Â Emergency Electric Service
1)Â Â Â Â Â Â Â Â To provide electricity during an interruption of the normal
electric supply, an emergency source of electricity shall be provided and
connected to the life safety branch, the critical branch, and the equipment
branch for lighting and power as established in NFPA 70-517.
2)Â Â Â Â Â Â Â Â The source of this emergency electric service shall be as
follows:
A)Â Â Â Â Â Â Â An emergency generating set when the normal service is supplied
by one or more central station transmission lines.
B)Â Â Â Â Â Â Â An emergency generating set or a central station transmission
line when the normal electric supply is generated on the premises.
3)Â Â Â Â Â Â Â Â Emergency Generating Set
A)Â Â Â Â Â Â Â The required emergency generating set, including the prime
mover and generator, shall be located on the premises. Where stored fuel is
required for the emergency generator operations, the storage capacity shall be
sufficient for not less than 24 hours continuous operation.
B)Â Â Â Â Â Â Â The emergency generator set may be used during periods of high
energy demands on local utilities. In the event of an outage of the normal
power source, the normal loads shall immediately be removed from the emergency
generator set, and the life safety branch, the critical branch, and the
equipment branch shall be connected to the generator.