77 Ill. Adm. Code 860.270
Fire Safety
Section 860
Section 860.270 Fire Safety
a) Bales of straw or other flammable materials that do not meet
the requirements of subsection (b) of this Section shall not be used for
skirting or insulation of the manufactured home. (Type B Violation)
b) Garages, carports, porches, awnings, sheds, skirting and other
similar appurtenances shall be constructed of material designed for exterior
use that meets the flame spread rating of 200 or less in accordance with the
American Society of Testing and Materials, Standard Method of Test for Surface
Burning Characteristics of Building Materials (Standard E84). (Type B
Violation)
c) Fire
Hydrants
1) If a
manufactured home community has fire hydrants, the fire hydrant valves shall be
tested annually and the flow rates documented annually by the local fire department,
water department or other entity capable of analyzing the available flow from
the hydrants. Such test results shall be available to the Department upon
request. (Type A Violation)
2) The
licensee shall provide notification in writing to the local fire department of
the hydrants that have been deemed unsatisfactory, which includes an agreement
to either remove the hydrants, reverse the top of the hydrant or provide some
other identification acceptable to the fire department to indicate that the
hydrant is not acceptable, or install a system that meets the requirements of subsection
(d). (Type A Violation)
3) The
residents of the manufactured home community shall be advised in writing by the
licensee within 30 days when a manufactured home community licensee becomes
aware that one or more hydrants in the community is inadequate. The location
of these fire hydrants shall be specified in writing, along with a plan to
correct the situation and an anticipated date for completion. The hydrant
shall be repaired or replaced within 30 days. A copy of the notification shall
be provided to the Department's Springfield office. (Type A Violation)
d) Manufactured home communities constructed after July 1, 2005
must be located in an area protected by a fire department or fire protection
district and provided with fire hydrants within 500 feet of any structure in
the manufactured home community. As an alternative to fire hydrants, a holding
pond or other source of water of 100,000 gallons or more accessible to the fire
department or fire protection district may be used, if the fire department or
fire protection district is capable of pumping from the body of water. The
minimum size water main for providing fire protection shall be six inches in
diameter. The system shall be designed to maintain a minimum pressure of 20
psi at all points in the distribution system under normal conditions of flow.
(See Table B.) (Type A Violation)
e) Flammable liquids and gasoline-powered equipment other than
motorized vehicles shall not be stored within five feet of a manufactured home,
except when stored in a shed or garage. (Type B Violation)
f) All intended means of egress shall not be obstructed. (Type C
Violation)