77 Ill. Adm. Code 810.140
Electrical Safety
Section 810
Section 810.140Â Electrical
Safety
a)        New Installations. All electrical distribution systems
constructed after July 1, 2023, shall be designed, constructed and maintained
in accordance with the National Fire Protection Association's National
Electrical Code 2017 edition (NFPA 70-2017).
b)        Existing Installations. The following minimum requirements
shall apply at any and all portions of electrical systems installed prior to
July 1, 2023:
1)        Conductors. The type and size of all conductors shall comply
with their approved use as indicated in the National Electrical Code (NFPA
70-1984).
2)        Overcurrent Protection. All electrical power distribution
system conductors in youth camps shall be protected against overcurrent by
circuit breakers or fuses sized for the rated current carrying capacity of the
conductors.
3)        Receptacles. Receptacles serving recreational vehicles shall
be of the grounding type of either 5, 20, 30 or 50 amps. When tested by a
receptacle tester, they shall not indicate any open ground, open neutral or
open hot conductors or any reversed wiring conditions.
4)        Weatherproof Equipment. All switches, circuit breakers,
receptacles, control equipment, junction boxes, and metering devices located
outside shall be weatherproof equipment when in use or a cover must be placed
over them so they are weatherproof when in use.
5)        Splices. All electrical power distribution feeders shall be
continuous from fitting to fitting, and all splices shall comply with the
National Electrical Code (NFPA 70-1984).
6)Â Â Â Â Â Â Â Â Clearances.
A)Â Â Â Â Â Â Â In areas that are subject to movement of vehicles, overhead
electrical power distribution wiring shall be at least 15 feet above grade. In
areas that are not subject to movement of vehicles, overhead electrical power
distribution wiring shall be at least 10 feet above grade, sidewalks,
platforms, or any projections from which they may be reached.
B)Â Â Â Â Â Â Â A horizontal clearance of three feet shall be maintained
between vehicles and the support for overhead conductors.
C)Â Â Â Â Â Â Â Outdoor receptacles shall be located at least 18 inches above
ground level.
7)        Adequacy of Supports. Any structure used to support
electrical wiring or equipment shall be capable of supporting the required
structural loads. Electrical equipment shall not be attached to trees.
8)        Tree Branches. Dead Tree branches which overhang distribution
wiring shall be removed and live branches which touch distribution wiring shall
be trimmed.
c)Â Â Â Â Â Â Â Â All electrical systems shall be maintained in a safe state of
repair. All damaged or defective equipment shall be repaired or replaced. All
loose equipment shall be secured. All face plates and panel fronts shall be in
place and all live parts shall be covered to prevent accidental contact. All
components of the electrical system shall be periodically inspected by the
licensee to determine if they are properly functioning.