77 Ill. Adm. Code 820.340
Operation and Maintenance
Section 820
Section 820.340Â Operation
and Maintenance
a)Â Â Â Â Â Â Â Â Swimming Facility
1)Â Â Â Â Â Â Â Â The pool and aquatic features shall be maintained free from
sediment, lint, dirt and hair. Cracks and other defects in the pool and
aquatic features shall be repaired. The walls, ceilings, floors, equipment and
swimming facility proper shall be maintained so that they are protected from
deterioration. All equipment shall be maintained in proper condition, with all
required components in place. Equipment required to be NSF Standard 50
certified, including filters, skimmers and chemical feeding equipment, shall
not be altered or modified in any way.
2)        Swimming facility decks shall be rinsed daily. Indoor swimming
facility decks shall be disinfected at least weekly. The walks, overflow
gutters, counters, lockers, equipment, furniture, interior partitions and walls
shall be kept in good repair, clean, and sanitary. No furniture, plants or
other furnishings shall be placed within 4 feet of the swimming facility. This
area shall be kept free of obstructions such as chairs and baby strollers. The
deck shall be kept free of tripping hazards, such as deck surface
irregularities, hoses, baby strollers, and maintenance equipment. The deck,
walkways and floors shall be free of areas with poor drainage that retain
water.
3)Â Â Â Â Â Â Â Â Floats or tubes not in use shall be removed from the swimming
facility.
4)        Starting Platforms. Starting blocks shall not be used for any
purpose other than competitive swimming activities. Starting blocks shall be
securely anchored when in use but removed or prohibited from use when not being
used in conjunction with competitive swimming or training. The maximum height
of the platform above the water shall be 30 inches where the water depth is 4
feet or greater and 20 inches when the water depth is less than 4 feet.
5)Â Â Â Â Â Â Â Â Safety ropes shall be kept in place except when the swimming facility
is being used exclusively for lap swimming or competition.
6)Â Â Â Â Â Â Â Â Access to grass areas shall be prevented when bare areas
develop, when the grass is not regularly maintained, when debris is allowed to
accumulate, or an unsightly condition, offensive odor, or a muddy condition
exists.
b)        Perimeter Overflow, Suction Outlet Covers and Skimmers. The
perimeter overflow systems, suction outlet covers or automatic surface skimmers
shall be clean and free of leaves or other debris that would restrict flow.Â
The strainer baskets for skimmers shall be cleaned daily. Broken or missing
skimmer weirs shall be replaced. Broken or missing suction outlet covers shall
be replaced immediately and installed in accordance with the manufacturer's
requirements. The flow through each skimmer shall be adjusted as often as
necessary to maintain a vigorous skimming action that will remove all floating
matter from the surface of the water. The pool water shall be maintained at an
elevation so that effective surface skimming is accomplished. A higher water
level may be maintained during official swimming competition. For pools with
perimeter overflow systems, adequate surge storage capacity shall be maintained
so that flooding of the perimeter overflow system does not occur during periods
of peak usage. The flow returning from the pool shall be balanced or valved so
that the majority of flow is returned through the perimeter overflow or skimmer
system.
c)        Inlet Fittings. Inlets shall be checked frequently so that
the rate of flow through each inlet establishes a uniform distribution
pattern. Inlets in pools with surface skimmers shall be adjusted as necessary
to provide vigorous skimming.
d)Â Â Â Â Â Â Â Â Bather Preparation Facilities
1)Â Â Â Â Â Â Â Â Floors shall be cleaned and disinfected daily.
2)Â Â Â Â Â Â Â Â Toilet rooms and fixtures shall be kept clean, free of dirt
and debris and in good repair. Floors shall be maintained in a slip-resistant
condition. Soap dispensers shall be filled and operable. A supply of toilet
paper shall be provided at each toilet at all times.
e)        Foot Baths. Foot baths shall be free of dirt, debris and
other floating matter and shall be operated by continuously introducing fresh
water and discharging used water to waste.
f)        Security. Doors or gates in the swimming facility enclosure
shall be kept closed and locked when the swimming facility is closed.
g)        Bather Loads. The number of persons within a swimming facility
enclosure shall not exceed the permissible bather load established by the
Department. Additional patrons may be allowed at other recreational features
within the swimming facility enclosure, such as sand play areas, turf
sun-bathing areas and picnic areas, if additional toilet facilities are
provided. However, the number of patrons in swimming facilities or their decks
shall not exceed the bather load.  The bather load shall be posted at the swimming
facility entrance or at a location where it can be seen by all patrons and
shall be enforced by the manager/operator.
h)Â Â Â Â Â Â Â Â Electrical Systems. Electrical systems shall be maintained in
accordance with the National Electrical Code.
i)         Diving Equipment. Diving equipment shall be maintained in a
safe condition, be securely anchored, and have a slip-resistant surface.
j)         Vacuum Cleaners. Vacuum cleaning shall not be conducted when
the swimming facility is in use.
k)Â Â Â Â Â Â Â Â Operation of Mechanical Equipment
1)Â Â Â Â Â Â Â Â Manufacturers' instructions for operation and maintenance of
mechanical and electrical equipment, as well as pump performance curves, shall
be kept available at the swimming facility. All valves and piping in the
equipment room shall be permanently identified as to use and direction of
flow. A valve operating procedure shall be provided in the equipment room for
each operation (e.g., recirculation, filtration, backwashing).
2)Â Â Â Â Â Â Â Â Pumps, filters, disinfectant feeders, flow indicators, gauges,
and all related components of the swimming facility water recirculation system
shall be kept in continuous operation 24 hours a day. A recirculation and
filtration flow rate that will result in a turnover period as specified in
Section 820.210 shall be maintained at all times. For wading areas in swimming
facilities constructed prior to May 20, 1999 where the specified flow rate
cannot be attained without alteration of the recirculation system, a
recirculation flow rate that will result in a turnover period of no more than 6
hours shall be maintained in the wading area.
3)        Recirculation Pumps. The pump shall not be throttled on the
suction side during normal operation except for necessary regulation of flow
through main drain piping. Recirculation pumps shall be kept in good repair
and condition. The pump discharge or inlet supply line valve shall be adjusted
as necessary to maintain the design flow rate.
4)Â Â Â Â Â Â Â Â Filtration
A)Â Â Â Â Â Â Â The filtration flow rate shall not exceed the maximum
filtration design flow rate specified by the filter manufacturer for public
swimming facility use in accordance with NSF Standard 50. If this rate is not
known or has not been determined, the flow rate shall not exceed 15 gallons per
minute per square foot of filter area for high-rate sand filters, 3 gallons per
minute per square foot for other sand filters, 1.5 gallons per minute per
square foot for diatomaceous earth filters, or 0.375 gallons per minute per
square foot for cartridge filters. A filtration flow rate of up to 2.0 gallons
per minute per square foot may be allowed where continuous feeding of
diatomaceous earth is used with a diatomaceous earth filter in accordance with
subsection (k)(3)(C)(iii).
B)Â Â Â Â Â Â Â Sand Filters
i)Â Â Â Â Â Â Â Â Â The filter air release valve shall be opened as necessary, to
remove air that collects in the filter, and following each backwash.
ii)Â Â Â Â Â Â Â Â The filter shall be backwashed when the design flow rate can
no longer be achieved, or when specified by the filter manufacturer, whichever
occurs first.
C)Â Â Â Â Â Â Â Diatomaceous Earth Filters
i)         The dosage of diatomaceous earth pre-coat shall be at least 1½
ounces per square foot of element surface area. Pressure diatomaceous earth
filters shall be backwashed when the design flow rate can no longer be achieved
or when specified by the filter manufacturer, whichever occurs first. Whenever
the recirculation pump stops or is shut off, the filter shall be thoroughly
backwashed and the elements shall be pre-coated before placing the pump back
into operation. Vacuum diatomaceous earth filters shall be washed when the
design flow rate can no longer be achieved or when specified by the filter
manufacturer, whichever occurs first. Backwashing shall not be performed when
the swimming facility is in use.
ii)Â Â Â Â Â Â Â Â During the pre-coating operation, either the initial filter
effluent shall be recirculated through the filter until the filter effluent is
clear, or the initial filter effluent shall be discharged to waste until
properly clarified water is produced.
iii)Â Â Â Â Â Â Â When continuous diatomaceous earth feed is used so that a
filter may be operated at a filtration rate higher than would otherwise be
allowable, it shall be applied at a rate of ½ to 1½ ounces per square foot of
surface area per day, or as needed to extend filter cycles.
D)       Cartridge Filters. A clean extra set of filter cartridges
shall be available at the swimming facility.
5)        Hair and Lint Strainers. Hair and lint strainers shall be
cleaned to prevent clogging of the suction line and cavitation. The pump shall
be stopped before the strainer is opened to avoid drawing air into the pump and
losing the prime. In the case of diatomaceous earth filters, the hair strainer
basket shall be cleaned immediately prior to pre-coating the filter.
6)        Flow Meters. Flow meters shall be maintained in an accurate
operating condition and shall be readable.
7)        Vacuum and Pressure Gauges. The lines leading to the gauges
shall be bled occasionally to prevent blockage.
8)Â Â Â Â Â Â Â Â Gas Chlorinators
A)Â Â Â Â Â Â Â Gas chlorinators shall be repaired only by a person trained in
servicing these units. The manager/operator shall post the telephone numbers
of the appropriate emergency personnel to contact in a chlorine gas emergency.
B)Â Â Â Â Â Â Â Chlorine cylinders shall be stored indoors in the area designed
for that purpose and away from a direct source of heat. They shall be chained
or strapped to a rigid support to prevent accidental tipping. Cylinders shall
not be moved unless the protection cap is secured over the valve. A gas mask
that is approved by the National Institute of Occupational Safety and Health
(NIOSH) or Mine Safety and Health Administration (MSHA) for use in a chlorine
atmosphere shall be kept outside the chlorine room in an unlocked container at
all times. The gas mask canister shall be replaced regularly per the
manufacturer's recommendations.
C)Â Â Â Â Â Â Â Chlorinators, gas lines, injectors, vent lines and cylinders
shall be checked daily for leaks. In case of a chlorine leak, corrective
measures shall be undertaken only by trained persons wearing proper safety
equipment. All other persons shall leave the dangerous area until conditions
are again safe.
9)Â Â Â Â Â Â Â Â Positive Displacement Feeders
A)Â Â Â Â Â Â Â Positive displacement feeders shall be periodically inspected
and serviced.
B)Â Â Â Â Â Â Â When a chemical feeder is used with calcium hypochlorite
solution, to minimize sludge accumulation in the unit, the lowest practicable
concentration of solution shall be used, and this concentration shall not exceed
5 percent (about 20 pounds of 65 percent chlorine powder in 50 gallons of
water). If liquid chlorine solution is used, the dilution with water is not critical
to the operation of the unit. After first thoroughly rinsing with water, a
small amount of mild acid solution may be fed through the unit periodically to
dissolve sludge accumulations.
10)        Safety Vacuum Release System and Safety Vent Pipe. Safety
vacuum release systems shall be maintained in operable conditions and in
accordance with the manufacturer's requirements. Safety vent pipes and
atmospheric vents for gravity drainage systems shall be maintained free of
blockages.
l)         Chlorinated Cyanurates. The use of chlorinated cyanurates is
subject to the following requirements:
1)Â Â Â Â Â Â Â Â Superchlorination shall be accomplished by using a chlorine
product other than a cyanurate; and
2)Â Â Â Â Â Â Â Â When the cyanuric acid level exceeds the maximum permissible
limit of 100 p.p.m., 50 percent of the water shall be drained and replenished
with potable water until the cyanuric acid concentration is less than 50 p.p.m.
m)Â Â Â Â Â Â Â pH Adjustment
1)Â Â Â Â Â Â Â Â Soda ash or caustic soda may be used to raise the swimming
facility water pH.
2)Â Â Â Â Â Â Â Â Caustic soda shall be used only in accordance with the
manufacturer's instructions. Protective equipment and clothing, including
rubber gloves and goggles, shall be available for the handling and using this
chemical.
3)Â Â Â Â Â Â Â Â Sodium bisulfate, carbon dioxide gas or muriatic acid shall be
used to lower swimming facility water pH. Carbon dioxide cylinders shall be
securely chained or otherwise restrained in a manner that will prevent tipping.
4)Â Â Â Â Â Â Â Â Hydrochloric (muriatic) acid shall be used only in accordance
with the manufacturer's instructions. Protective equipment and clothing,
including rubber gloves and goggles, shall be available for handling this
chemical.
5)Â Â Â Â Â Â Â Â The Department shall be consulted if unusual pH problems occur,
including corrosion or scaling or wide fluctuations in pH.
n)Â Â Â Â Â Â Â Â Algae Control
1)Â Â Â Â Â Â Â Â Algae shall be eliminated by superchlorinating to 10 p.p.m.
and maintaining this level for several hours. The swimming facility shall not
be open for use during this treatment. If this fails to eliminate the algae,
the Department shall be consulted for further advice.
2)Â Â Â Â Â Â Â Â Treated algae that cling to the floor and sides of the swimming
facility shall be brushed loose and removed by the suction cleaner and
filtration system.
o)Â Â Â Â Â Â Â Â Miscellaneous Chemicals
1)Â Â Â Â Â Â Â Â Chemicals shall be kept covered and stored in the original
labeled container, away from flammables and heat and in a clean, dry,
well-ventilated place that prevents unauthorized access to the chemicals.
2)Â Â Â Â Â Â Â Â The chemicals used in controlling the quality of water shall
be used only in accordance with the manufacturer's instructions.
3)Â Â Â Â Â Â Â Â If polyphosphates are used for sequestering iron, the
concentration of polyphosphates shall not exceed 10 p.p.m.
p)        Acoustics. If noise is excessive, so that safety instructions
cannot be heard, corrective action shall be taken.
q)Â Â Â Â Â Â Â Â Slides
1)Â Â Â Â Â Â Â Â Water slide equipment shall be maintained in a safe condition
and securely anchored.
2)Â Â Â Â Â Â Â Â Only one rider at a time shall be allowed to enter a slide,
unless the slide is designed by the manufacturer for two or more riders.
3)Â Â Â Â Â Â Â Â For water slides and drop slides, if the plunge area is not
visible from the top of the slide, a means of communication shall be provided
between the attendant at the top and the lifeguard at the bottom.
4)Â Â Â Â Â Â Â Â At the entrance to water slides and drop slides, a sign shall
be posted at the top of the slide warning all sliders not to proceed down the
slide until instructed to do so by the slide attendant.