77 Ill. Adm. Code 855.240
Reestablishment of the Work Area and HVAC Systems in Commercial and Public Buildings
Section 855
Section 855.240Â
Reestablishment of the Work Area and HVAC Systems in Commercial and Public
Buildings
The contractor, building owner,
or the building owner's representative shall reestablish the work area in
accordance with the following procedures:
a)Â Â Â Â Â Â Â Â Reestablishment of the work area shall only occur following
the completion of the cleanup procedures and after clearance air monitoring has
been performed and documented to the satisfaction of the school board or
building owner.
b)Â Â Â Â Â Â Â Â The contractor, the building owner or the building owner's
designee shall visually inspect the work area for any remaining visible
residue. Evidence of contamination shall necessitate additional cleaning.
c)Â Â Â Â Â Â Â Â Additional air monitoring shall be performed if additional
cleanup is necessary.
d)Â Â Â Â Â Â Â Â Following completion of clearance air monitoring of the work
area, remaining equipment and polyethylene barriers shall be removed and
disposed of as asbestos-contaminated waste. Following removal, the entire
area, including HVAC filter assembly and outside of the duct work, shall be wet
cleaned or HEPA vacuumed to remove residual asbestos fibers.
e)Â Â Â Â Â Â Â Â Mounted objects removed from former positions during area
preparation activities may be resecured.
f)Â Â Â Â Â Â Â Â Objects that were removed to temporary locations may be
relocated to original positions.
g)Â Â Â Â Â Â Â Â New filters shall be installed in HVAC systems, as necessary,
and mechanical and electrical systems shall be reestablished in working order.