77 Ill. Adm. Code 890.1010
Indirect Waste Piping
Section 890
Section 890.1010Â Indirect
Waste Piping
a)        Food and Beverage Handling. Commercial dishwashing machines,
dishwashing sinks, pot-washing sinks, pre-rinse sinks, silverware sinks, bar
sinks, soda fountain sinks, vegetable sinks, potato peelers, ice machines,
steam tables, steam cookers and other similar fixtures shall have their drain
lines indirectly discharged to a proper receptor. The only exception shall be
when the fixtures are located adjacent to a floor drain. The waste may be
directly connected on the sewer side of the floor drain trap provided that the
fixture waste is trapped and vented as required by this Part (see Appendix H.Illustrations
A and B), and the floor drain is located within 4 feet horizontally of the
fixtures and in the same room. In the case of direct connection, no other
fixture waste shall be connected between the floor drain trap and the fixture being
protected. All indirect waste shall discharge to a vented trap located as close
as possible to the fixture and in the same room. (See Appendix H.Illustrations
C and D.)
b)        Connection. Indirect waste connections shall be provided for
drains, overflows and relief valves from the water supply system. (See
Appendix H.Illustration E.) A clear water waste shall discharge through an
indirect waste into a sanitary or storm drain system located on the same floor.
c)        Sterile Materials. Stills, sterilizers and other appliances,
fixtures, devices and water and waste connections used for preparation of
sterile material shall be indirectly discharged to the drainage system.
d)        Swimming Pools. When backwash or other waste water from a
swimming pool filter discharges to the sanitary waste system, it shall be
indirectly wasted. When deck drains around a pool discharge to the sanitary
waste system, they shall be indirectly wasted.
e)        Clear Water Wastes. Water lifts, expansion tanks, cooling
jackets, sprinkler systems, drip or overflow pans, refrigerated cases, or
similar devices that discharge only clear water shall discharge indirectly into
a building storm drain or building drain located on the same floor, or into a
vacuum waste system.
f)Â Â Â Â Â Â Â Â Fire Sprinkler Systems. Â The relief valve (port) of a backflow
device located on a fire sprinkler system that contains an additive shall drain
indirectly to the building drain.
g)        Cleaning. Indirect waste piping shall be installed so as to
permit access for flushing and cleaning.