77 Ill. Adm. Code 890.1190
Water Supply Control Valves and Meter
Section 890
Section 890.1190Â Water
Supply Control Valves and Meter
a)Â Â Â Â Â Â Â Â A full-port shut-off valve shall be located near the curb or
property line and immediately inside the building, on the inlet and outlet side
of the water meter. When located underground, this valve shall be in a stop
box or meter vault. (See Appendix I.Illustration H.)
b)Â Â Â Â Â Â Â Â The utility meter may be installed outside in an accessible
meter vault or within the building. The meter shall have unions on the inlet
and outlet openings. A full-port valve with an open area at least that of the
water service shall be provided for all meters and shall be provided with a
drain valve installed on the discharge side of the meter valve when located
inside of a building. (See Appendix I.Illustrations H and I.)
c)        Tank Controls. Supply lines taken from pressure or gravity
tanks shall be valved at or near their source.
d)        Water Heating Equipment. A shut-off valve shall be provided
in the cold water branch within 5 developed feet of each water storage tank or
each water heater and located in the same room.
e)        Separate Controls for Each Family Unit. In multiple family
dwellings, the water service or water distribution pipe to each family unit
shall be controlled by an arrangement of line valves that permits each group of
fixtures and each individual fixture to be shut off without interference with
the water supply to any other family unit or portion of the building. The
location of these valves shall be uniform in each family unit of a multiple
family dwelling. (See Appendix I.Illustration J.)
f)        Buildings Other Than Dwellings. In all buildings other than
dwellings and health care facilities as specified in subsection (g), line
valves shall be installed to permit the water supply to all equipment or
fixtures in each separate room to be shut off without interfering with the
water supply to any other room or portion of the building. For plumbing
equipment or fixtures that are installed back-to-back in adjacent rooms, e.g.,
in adjacent restrooms, a common line valve may be used to shut off the water
supply to the back-to-back fixtures in no more than two adjacent rooms. (See
Appendix I.Illustration K.)
g)        Health Care Facilities. In the residence rooms of health care
facilities, the water distribution pipe to each resident unit shall be
controlled by an arrangement of line valves that permits each group of
fixtures, and each individual fixture, to be shut off without interference with
the water supply to any other unit or portion of the building.