77 Ill. Adm. Code 890.1210
Design of a Building Water Distribution System
Section 890
Section 890.1210Â Design of a
Building Water Distribution System
a)        Design and Installation. The design and installation of the
hot and cold water building distribution systems shall provide a volume of
water at the required rates and pressures to ensure the safe, efficient and
satisfactory operation of fixtures, fittings, appliances and other connected
devices during periods of peak use. No distribution pipe or pipes shall be
installed or permitted outside of a building or in an exterior wall or attic unless
the pipe is protected from freezing.
b)        Size of Water Distribution Pipes. The fixture supply for each
fixture shall be at least the minimum size provided in Appendix A.Table D. The
size of all other water distribution pipes shall be determined by calculating
the water supply demand (in water supply fixture units) for that portion of the
water distribution system served by the pipe. Using Appendix A.Tables M, N, O,
P and Q, the cumulative water supply demand or load shall be calculated for all
fixtures, piping, valves and fittings served by the water distribution pipe,
and the pipe shall meet the minimum size provided in Appendix A.Table N or O,
as applicable. Exception: As an alternative to using Tables M, N, O, P and Q
to design and size the piping in the water distribution system, the system may
be designed and sized employing current engineering practices, provided that the
design/plans are approved in writing by an Illinois licensed professional
engineer, an Illinois licensed architect or an individual Certified in Plumbing
Design (CPD) by the American Society of Plumbing Engineers and approved in
writing by the Department.
c)        Minimum Water Pressure. The minimum constant water service
pressure on the discharge side of the water meter shall be (at least) 20 psi,
and the minimum constant water pressure at each fixture shall be at least 8 psi
or the minimum recommended by the fixture manufacturer.
d)        Auxiliary Pressure. Supplementary Tank. If the pressure in
the system is below the minimum 8 psi at the highest water outlet when the flow
in the system is at peak demand, an automatically controlled pressure tank or
gravity tank of a capacity to supply sections of the building installation that
are too high to be supplied directly from the public water main shall be
installed.
e)        Low Pressure Cut-Off. When a booster pump, except those used
for fire protection, is used on an auxiliary pressure system, a low-pressure
cut-off switch shall be installed on the booster pump to prevent the creation
of pressures less than 5 psi on the suction side of the pump. A shut-off valve
shall be installed on the suction side of the water system and within 5 feet
from the pump suction inlet, and a pressure gauge shall be installed between
the shut-off valve and pump.
f)        Water Hammer. All building water supply systems shall be provided
with air chambers or approved mechanical devices or water hammer arrestors to
absorb pressure surges. Water pressure absorbers shall be installed at the
ends of long pipe runs or near batteries of fixtures.
1)        Air Chambers − An air chamber that is installed in a
fixture supply shall be at least 12 inches in length and the same diameter as the
fixture supply, or an air chamber with an equivalent volume may be used. Â An
air chamber that is installed in a riser shall be at least 24 inches in length
and at least the same size as the riser.
2)        Mechanical Devices − If a mechanical device or water
hammer arrestor is used, the manufacturer's specifications for location and
installation shall be followed.
g)Â Â Â Â Â Â Â Â Excessive Static Water Pressure
1)Â Â Â Â Â Â Â Â If water main pressure exceeds 80 psi, a pressure reducing
valve and a strainer with a by-pass relief valve shall be installed in the
water service pipe near the entrance to the building to reduce the water
pressure to 80 psi or lower, except where the water service pipe supplies water
directly to a water pressure booster system, an elevated water tank, or to
pumps provided in connection with a hydropneumatic or elevated water supply
tank system. Sill cocks and outside hydrants may be left on full water main
pressure.
2)Â Â Â Â Â Â Â Â When the water pressure exceeds 80 psi at any plumbing
fixture, a pressure reducing valve, pressure gauge and a strainer with a
by-pass relief valve shall be installed in a water supply pipe serving the
fixture to reduce the water pressure at the fixture to 80 psi or lower.
h)        Approval of Auxiliary Pressure Systems. Whenever, in any
building, structure or premises receiving its potable water supply from the
public water system, a pump or any other device for increasing the water
pressure is to be installed, installation plans shall be approved by the
Department prior to installation in accordance with Section 890.1940.
i)         Variable Street Pressures. If the water main has a wide
fluctuation in pressure, the water distribution system shall be designed for
minimum pressure available at the main.