77 Ill. Adm. Code 890.1320
Drainage System Installation
Section 890
Section 890.1320Â Drainage
System Installation
a)        Drain – Underground. A building drainage system installed in the
ground shall be of cast iron, copper Type "K", or non-metallic
Schedule 40 or heavier. Drains shall be installed on a continuous bed of
undisturbed earth or granular fill so as to support the pipe and fittings.
b)        Existing Drain and Sewer Installation. Existing drain, waste,
vent and sewer may be used in the renovation of the plumbing system of an
existing structure if they are in serviceable condition and the materials comply
with Appendix A.Table A (Approved Building Drainage/Vent Pipe and Approved Materials
for Building Sewer).
c)        Freezing. No soil or waste pipe shall be installed or
permitted outside of a building or in an exterior wall unless the piping is
protected from freezing. This does not prohibit a soil or waste pipe from
extending from a manufactured or mobile home unit to an approved point of
discharge, provided that the waste line is protected from freezing.
d)        Dead Ends. Dead ends shall be avoided in a drainage system,
except where necessary to extend the system to install a cleanout in an
accessible location. A dead end intended for future connection (extension) that
is more than 2 feet above a floor or more than 10 feet horizontally from the
nearest vented connection shall have a vented connection to the outside
atmosphere. (See Appendix J.Illustration A.)
e)        Horizontal Drainage Piping. Horizontal drainage piping shall
be installed at a uniform grade.
f)        Small Piping. Horizontal drainage piping of 3 inches diameter
or less shall be installed with a grade of at least ¼-inch per foot.
g)        Large Piping. Horizontal drainage piping larger than 3 inches
but less than 8 inches in diameter shall be installed with a grade of at least â…›-inch
per foot. For piping 8 inches or larger in diameter, the grade is determined
by the number of drainage fixture units connected to the drain pipe. (See
Appendix A.Table G.)
h)        Minimum Velocity. If conditions do not permit building drains
to be installed with a grade as great as that specified in subsections (f) and
(g), a lesser grade may be used, provided that the computed velocity will not
be less than 2 feet per second.
i)         Changes in Direction. Changes in direction shall be made in
drainage piping by the use of 45 degree wyes, long sweeps, short sweeps,
quarter, fifth, sixth, eighth, or sixteenth bends, or by a combination of these
fittings. Single and double sanitary tees and short sweep quarter bends shall
be used in drainage lines only where the direction of flow is from the
horizontal to the vertical and may be used for making necessary vertical
offsets between the ceiling and floor above. (See Appendix J.Illustrations B, C
and D.)Â Exception:Â A short sweep drainage quarter bend of less than 3 inches
diameter and placed in a horizontal to horizontal position for a stack vent arm
may be used to receive graywater.
j)Â Â Â Â Â Â Â Â Â No fittings having a hub in the direction opposite to flow,
or tee branch, shall be used as a drainage fitting. No running threads, bands
or saddles shall be used in the drainage system. No drainage or vent pipe or
fitting shall be drilled or tapped.
k)Â Â Â Â Â Â Â Â No fitting, connection, device or method of installation shall
be used that obstructs or retards the flow of water, waste or air in the
drainage or venting system by an amount greater than the normal frictional
resistance to flow. The enlargement of a 3-inch closet bend or stub to 4 inches
shall not be considered an obstruction if it is necessary to increase the bend
or stub at the floor line to 4 inches in diameter to accommodate the water
closet outlet.
l)         Fixture Connections. Branch wastes and fittings for circuit-vented
fixtures shall be installed so that the fixture drain enters the side of the
branch drain. (See subsection (i) and Appendix J.Illustration E.)
m)       Back-to-Back Fixtures. Back-to-back fixtures shall be
installed with fittings that will prevent mixing of the discharge prior to a
change in direction of flow of the discharge from each fixture, or shall be
installed with fittings especially designed to eliminate throw-over or backflow
of the discharge from one fixture to the other fixture.
n)        Location of Drains. All building drains, branches of building
drains, building sewers or any sanitary sewers shall be located at least 50
feet from a well or buried suction line, except that, when cast iron pipe with
mechanical or compression joints or Schedule 40 PVC pipe with solvent weld and watertight
joints is used for the building sewer, the drains shall be located at least 10 feet
from a well or buried suction line.
o)Â Â Â Â Â Â Â Â Backwater valves may be installed in the building storm drain
or the building drain to prevent backflow into the building, where backflow of
storm water or sewage could occur. Backwater valves may be installed in the
branches of the building drain that are below grade. Backwater valves, when
fully opened, shall have a capacity of at least that of the pipes in which they
are installed. Backwater valves shall be installed to be accessible. All
backwater valves shall conform to ASME A112.14.1. All bearing parts of
backwater valves shall be made of corrosion-resistant material.