77 Ill. Adm. Code 890.1370
Floor Drains
Section 890
Section 890.1370Â Floor
Drains
a)        Required. Any building or structure in which plumbing fixtures
or piping is installed in or under a concrete floor to accommodate fixtures on
the level of the concrete floor shall have at least one trapped and vented floor
drain. Additional floor drains shall be required if the installation of
fixtures and appurtenances requires the use of floor drains. In a multi-family
dwelling, each unit shall have a floor drain if fixtures and appurtenances
installed in the dwelling require the use of a floor drain.
1)Â Â Â Â Â Â Â Â Underground floor drains connected to a building drain or a
building sub‑drain within 4 feet of a stack shall be individually
vented. All floor drains shall be vented as required by Appendix A.Table I.
2)Â Â Â Â Â Â Â Â Each floor drain shall be connected to a sanitary waste drain,
except those drains receiving only clear water discharges, which may be
connected to the sub-soil drainage system.
3)Â Â Â Â Â Â Â Â Any sump or hub drain for receiving clear water waste shall
extend 2 inches above the floor, and all indirect clear water waste lines shall
be above the floor level. Any floor drain level with the floor shall discharge
to a sanitary waste drain. (See Appendix A.Tables F and I.)
4)Â Â Â Â Â Â Â Â At least one floor drain shall be located in every restroom
having a masonry or concrete floor except those for private use.
5)Â Â Â Â Â Â Â Â In hospitals and nursing homes, floor drains will not be
required in toilet/bath facilities serving four or fewer individual residents
where access to the facilities is direct from no more than two resident rooms.Â
Toilet/bath facilities in hospitals and nursing homes serving rooms with more
than four residents or consisting of multiple toilets, lavatories, etc., are
required to have floor drains.
b)        Size. Each floor drain shall be sized for its intended use
and the surface area that it drains. Any floor drain or drain trap installed
below a basement floor or underground shall be no less than 2 inches in
diameter.
c)        Accessibility. Floor drains shall connect into traps, shall
be accessible and readily cleaned, and shall be located so that they are easily
visible.
d)        Provision for Evaporation. Floor drain seals subject to
evaporation shall be of the deep seal type, shall be fed by means of a priming
device designed for that purpose, or shall be filled with vegetable oil.
e)        Floor Drains in Food Establishments. Floor drains installed
in coolers, freezers, refrigerated holding areas, dressing rooms or processing
rooms shall meet the following requirements:
1)Â Â Â Â Â Â Â Â Floor drains shall have a minimum inside diameter of 4 inches.
2)Â Â Â Â Â Â Â Â Drainage lines from water closets and urinals shall not be
connected with any other sanitary drainage lines having floor drains located in
the food service establishments listed in subsection (e).
3)Â Â Â Â Â Â Â Â Floor drains shall be indirectly discharged to the drainage
system, or a backwater valve that conforms with the requirements of Section 890.1320(o)
shall be installed to isolate these floor drains from other sanitary discharges.
4)Â Â Â Â Â Â Â Â Floor drains shall comply with the requirements of subsections
(b), (c) and (d).