77 Ill. Adm. Code 890.1450
Vent Grades and Connections
Section 890
Section 890.1450Â Vent Grades
and Connections
a)        Grade. All vent and branch vent pipes shall be installed so
as to drain back to the soil or waste pipe. (See Appendix K.Illustration F.)
b)        Vertical Rise. Where vent pipes connect to a horizontal soil
or waste pipe, the vent shall be taken off above the center line of the soil or
waste pipe, and the vent pipe shall rise vertically, or at an angle not more
than 45 degrees from the vertical before offsetting horizontally or before
connecting to the branch vent. Exception: Wet vent and floor drain vents may
connect horizontally. (See Appendix K.Illustrations F, G and AA.)
c)        Height above Fixtures. The connection between a vent pipe and
a vent stack or stack vent shall be made at least 6 inches above the
flood-level rim of the highest fixture served by the vent. Horizontal vent
pipes forming branch vents or relief vents shall be at least 6 inches above the
flood-level rim of the highest fixture served. (See Appendix K.Illustration H.)
d)        Heel or Side-Inlet Bend. A heel or side-inlet quarter bend or
closet bend shall not be used as a dry vent when the inlet is placed in a
horizontal position. (See Appendix K.Illustration I.) Heel or side inlet
quarter or closet bends are permitted only in cases where the fixture
connecting is vented. (See Appendix K.Illustration I.)
e)Â Â Â Â Â Â Â Â All main vents or vent stacks shall connect full size at their
base to the building drain or to the main soil or waste pipe at or below the
lowest fixture branch. (See Appendix K.Illustration EE).