77 Ill. Adm. Code 890.1500
Installation of Wet Venting
Section 890
Section 890.1500Â
Installation of Wet Venting
a)Â Â Â Â Â Â Â Â The
following shall not be used to wet vent another fixture trap: water closets,
washing machine connections, blowout urinals, or dishwashers.
b)Â Â Â Â Â Â Â Â Two
lavatories with 1¼-inch traps shall be considered a single fixture for the
purpose of this Section.
c)Â Â Â Â Â Â Â Â A
vertical wet vent may be used for two fixtures set on the same floor level, but
connecting at different levels in the stack, provided that the vertical wet
vent/drain between the two traps is one pipe diameter larger than the upper
fixture trap and that both drains conform to Appendix A.Table I. (See Appendix
K.Illustration P.)
d)Â Â Â Â Â Â Â Â A
horizontal wet vent may be used for two fixtures set on the same floor level
with one fixture connecting upstream of the other fixture on the horizontal
line, provided that the horizontal wet vent/drain between the two fixtures is
one pipe diameter larger that the upstream fixture trap. The vent connection
shall be located between the traps, and each trap-to-vent distance shall be in
accordance with Appendix A.Table I. (See Appendix K.Illustration Q.)
e)Â Â Â Â Â Â Â Â A
vertical/horizontal wet vent may be used for two fixtures set on the same floor
level with one fixture connecting to the vertical stack and one fixture connecting
to the horizontal line, provided that the wet vent/drain is one pipe diameter
larger than the upper fixture trap and the drains conform to Appendix A.Table
I. (See Appendix K.Illustration R.)
f)Â Â Â Â Â Â Â Â A
single bathroom group of fixtures, consisting of a water closet, lavatory and a
bathtub, shower or floor drain, may be installed with the drain from a lavatory
serving as a wet vent for a bathtub, shower or floor drain and for the water
closet, provided that:
1)Â Â Â Â Â Â Â Â Not
more than four DFUs drain into a 2-inch diameter wet vent; and
2)Â Â Â Â Â Â Â Â The
horizontal branch is a minimum of 2 inches and connects to the stack at the
same level as the water closet drain. The horizontal branch may also connect to
the water closet bend. (See Appendix K.Illustration S.)
g)Â Â Â Â Â Â Â Â Bathroom
groups installed back-to-back consisting of two water closets, two lavatories,
and two bathtubs, showers or floor drains may be installed without individual
vents, provided that:
1)Â Â Â Â Â Â Â Â The
water closets are wasted to a proper vertical drainage fitting;
2)Â Â Â Â Â Â Â Â The
bathtubs, showers or floor drains connect to the stack at the same level as the
water closets;
3)Â Â Â Â Â Â Â Â The lavatories connect
to the stack at the same level; and
4)Â Â Â Â Â Â Â Â The
vent is a minimum of 2 inches in diameter. (See Appendix K.Illustration T.)
h)Â Â Â Â Â Â Â Â When bathroom groups are connected to the same soil stack, the
waste pipe from one or two lavatories may be used as a wet vent for one or two bathtubs
or showers, provided that:
1)Â Â Â Â Â Â Â Â The wet vent and its corresponding extension to the vent stack
are 2 inches in diameter;
2)Â Â Â Â Â Â Â Â Each water closet is provided with an individual dry vent or
vertical common vent; and
3)Â Â Â Â Â Â Â Â The
vent stack is sized as given in Appendix A.Table J. (See Appendix K.Illustrations
U and V.)
i)Â Â Â Â Â Â Â Â Â On the
lower floors of a multi-story building, a water closet may be wet vented with a
single lavatory in lieu of the requirements of Section 890.1470(h).
j)Â Â Â Â Â Â Â Â Â Bathroom
groups consisting of a water closet, lavatory, and bathtub or shower, connected
to a stack by a separate branch, may wet vent the water closet and bathtub or
shower with the lavatory, provided that:
1)Â Â Â Â Â Â Â Â The
water closet and bathtub/shower connect to the stack at the same level;
2)Â Â Â Â Â Â Â Â The
wet vent and its corresponding extension are a minimum of 2 inches in diameter;
and
3)Â Â Â Â Â Â Â Â A
vent stack connects at or below the lowest fixture connection and is installed
for a stack of this type. (See Appendix K.Illustration W.)