77 Ill. Adm. Code 890.1580
Size and Length of Vents
Section 890
Section 890.1580Â Size and
Length of Vents
a)        Size of Water Closet Vents. A water closet shall have at
least a 2-inch vent.
b)        Size of Individual Vents. The diameter of an individual vent
shall be at least 1¼ inches or at least half the diameter of the drain to which
it connects, whichever is greater.
c)        Size of Relief Vents. The diameter of a relief vent shall be
at least half the diameter of the soil or waste branch to which it is
connected.
d)        Size of Circuit Vents. The diameter of a circuit vent shall
be at least half the diameter of the horizontal soil or waste branch or the
diameter of the vent stack, whichever is smaller. (See Appendix A.Table L.)
e)        Size of Vent Piping. The size of vent piping shall be
determined based upon its length and the total number of drainage fixture units
connected to the vent pipe as provided in Appendix A.Table K. No more than 20
percent of the maximum developed length as determined from Table K may be
installed in the horizontal position. Vent piping serving floor drains shall be
installed so as to minimize horizontal vent distances.
f)Â Â Â Â Â Â Â Â Building Sub-drain Sump Pump Vent Sizes. Building sub-drain
sump pump vents shall be sized in accordance with Appendix A.Table K.
g)Â Â Â Â Â Â Â Â All
vents pipes shall extend undiminished in size from the vent connection or stack
cleanout through the roof to the outside atmosphere, or shall be reconnected
with a branch vent, vent stack, or stack vent.