77 Ill. Adm. Code 890.410
Fixture Traps/Continuous Waste
Section 890
Section 890.410Â Fixture
Traps/Continuous Waste
a)        Fixture Traps. All directly connected plumbing fixtures,
except those having integral traps, shall be separately trapped by a water-seal
trap, placed as close to the fixture outlet as possible. A kitchen sink with
up to three basins may be installed on one trap if one compartment is not more
than 6 inches deeper than the other and the waste outlets are not more than 30
inches apart. (See Appendix D.Illustration A.)
b)        Distance of Trap to Fixture. The developed length from the
fixture outlet to the trap weir shall not exceed 24 inches, except that an
interceptor used as a trap shall be located as close as possible to the
fixture. The maximum developed length from the fixture outlet to the inlet of
the interceptor shall not exceed 5 feet. (See Appendix D.Illustration B.) The
standpipe inlet for an automatic clothes washer shall not exceed 48 inches
above the weir of a trap.
c)        Trap Size. The size of trap for a fixture shall comply with
Appendix A.Table E for minimum size of traps. No trap shall be larger than the
fixture drain to which it is connected or the drainage pipe into which it
discharges.
d)        Type of Traps. Traps shall have a uniform and smooth
interior, and shall have no partitions or movable parts. The trap seal shall
be non-adjustable. (See Appendix D.Illustration C.)
e)Â Â Â Â Â Â Â Â Drum
Traps. Drum traps shall be 3 or 4 inches in diameter and provided with a fixed
water seal of at least 2 inches. The trap cleanout shall be one size less than
the trap diameter.
f)        Trap Seal. Each trap shall have a water seal of 2 inches
except where a deeper seal is required to prevent the loss of the trap seal by
evaporation. Where loss of the trap seal may occur due to evaporation, one of
the following shall be used:
1)Â Â Â Â Â Â Â Â Vegetable oil may be added to the trap.
2)Â Â Â Â Â Â Â Â A deeper seal not to exceed 8 inches may be used.
3)Â Â Â Â Â Â Â Â An automatic trap primer may be used.
g)Â Â Â Â Â Â Â Â Trap Cleanouts
1)Â Â Â Â Â Â Â Â Each fixture trap, except those cast integrally or in
combination with fixtures in which the trap seal is readily accessible or
except when a portion of the trap is readily removable for cleaning purposes,
shall have an accessible threaded or cam lock cleanout plug of ample size
protected by the water seal. (Exception: See subsection (g)(4).) The cleanout
plug shall be of brass or other non-corrosive type material. (See Appendix D.Illustration
D.)
2)Â Â Â Â Â Â Â Â Trap cleanouts shall be made gas and water-tight with a
threaded cleanout plug and approved washer.
3)Â Â Â Â Â Â Â Â A P-trap that is used on a bath waste shall be directly below
the tub overflow. The overflow shall be fastened to the tub by means other
than the face plate.
4)Â Â Â Â Â Â Â Â A P-trap on a plumbing fixture that is not accessible may be
installed without a cleanout plug or having a portion of the trap readily
removable, provided that there is access to a cleanout within 3 feet of the
trap.
h)        Trap Level and Protection. Traps shall be set level with
respect to their water seals and, where necessary, they shall be protected from
freezing.
i)         Traps Underground. Underground traps shall be provided with
accessible and removable cleanouts, except for separate "P" traps
into which floor drains, urinals and other fixtures with removable drain
strainers discharge.
j)         Building (House) Traps. No trap shall be installed at the
base of a soil or waste stack or in a building drain.
k)        Prohibited Traps. Use of the following traps is prohibited
(see Appendix D.Illustration E):
1)Â Â Â Â Â Â Â Â Traps that depend upon the action of movable parts for their
seal;
2)        Full "S" traps. Exception: Water closet and
similar fixtures that depend on self-siphonage for their proper operation;
3)Â Â Â Â Â Â Â Â Bell traps;
4)Â Â Â Â Â Â Â Â Crown vented traps;
5)Â Â Â Â Â Â Â Â Unvented running traps; and
6)Â Â Â Â Â Â Â Â Fixtures with concealed interior partitioned traps.Â
Exception: Fixtures with integral traps constructed of vitrified earthenware
and penal institutional fixtures with integral traps constructed of ferrous
material.
l)         Double Trapping. No fixture shall be double trapped.