77 Ill. Adm. Code 890.920
Vertical Piping
Section 890
Section 890.920Â Vertical
Piping
a)        Attachment. Vertical piping shall be secured at intervals to
keep the pipe in alignment and carry the weight of the pipe at its maximum
capacity. Stacks shall be supported at their base and, if over two (2) stories
in height, shall be supported at each floor by floor clamps. (See Appendix G:Â
Illustrations A and B.)
b)        Cast Iron Soil Pipe. Cast iron soil pipe shall be supported
at not less than every story height and at its base. Hubless or compression
gasket joint shall be supported at not less than every story height, at its
base and at intervals to keep the pipe in alignment and to adequately support
the weight of the pipe at its maximum capacity. (See Appendix G:Â Illustrations
A and B.)
c)        Threaded Pipe. Threaded pipe shall be supported at every
other story height. Supports shall be of ferrous material.
d)        Copper Tube. Hard drawn copper tube and annealed copper
tubing shall be supported at least every story at not more than ten (10) foot
intervals. On long lines where there are provisions for expansion and
contraction, anchors may be a maximum of four (4) stories apart for cold water
risers and drain/waste/vent (DWV) stacks, and two (2) stories apart for hot
water risers, provided there are sleeves or similar devices at intermediate
floors to restrain lateral movement. Supports shall be of copper material or
other material which will not react with the piping material, and which will
properly support the pipe.
e)        Lead Pipe. Lead pipe shall be supported at intervals not
exceeding four (4) feet. Supports shall be of lead or softer material.
f)        Plastic Pipe. Hangers and straps shall not compress, distort,
cut or abrade the piping and shall allow free movement of the pipe. Wire pipe
hooks shall not be used to support plastic pipe. Restraining joints and
expansion joints shall be installed as required. All vertical piping shall be
maintained in straight alignment with supports at each floor level or at
intervals of ten (10) feet, whichever is less. Trap arms in excess of three
(3) feet shall be supported as close as possible to the trap.