77 Ill. Adm. Code 890.APPENDIX A
A Plumbing Materials, Equipment, Use Restrictions and Applicable Standards
Section 885
Section 890.APPENDIX A
Plumbing
Materials, Equipment, Use Restrictions and Applicable Standards
Section 890.TABLE C
Minimum
Air Gaps for Plumbing Fixtures
Minimum
Air Gap (Inches)
When
Not
Affected by
Near Wall
1
When Affected by Near Wall
2
Lavoratories and other
fixtures with effective opening not greater than ½ inch diameter.
1
1½
Drinking water fountains,
single orifice not greater than
7
/
16
(0.437) inch
diameter or multiple orifices having total area of 0.150 square inches (area
of circle
7
/
16
inch diameter).
1
1½
Sink, laundry trays, goose
neck bath faucets and other fixtures with effective opening not greater than
one inch diameter.
1½
2¼
Stills, sterilizers and other
appliances, fixtures, devices and water and waste connections used for
preparation of sterile material.
2
3
Over rim bath fillers and
other fixtures with effective openings not greater than one inch diameter.
2
3
Effective openings greater
than one inch.
2
X Diameter of
effective
opening
3
X Diameter of
effective
opening
1
Side walls, ribs or other similar obstructions do not
affect air gaps when spaced from inside edge of spout opening a distance
greater than three times the diameter of the effective opening for a single
wall, or a distance greater than four times the diameter of the effective
opening for two intersecting walls.
2
Vertical walls, ribs or similar obstructions extending
from the water surface or to above the horizontal plane of the spout opening
require a greater air gap when spaced closer to the nearest inside edge of
spout opening than specified in Footnote 1 above. The effect of three or more
such vertical walls or ribs has not been determined. In such cases, the air
gap shall be measured from the top of the wall.