77 Ill. Adm. Code 890.APPENDIX A
A Plumbing Materials, Equipment, Use Restrictions and Applicable Standards
Section 890
Section 890.APPENDIX AÂ Â
Plumbing Materials, Equipment, Use Restrictions and Applicable Standards
Section 890.TABLE MÂ Â Load
Values Assigned to Fixtures
Fixture
Occupancy
Type of
Supply
Control
Load Values in Water (Supply
Fixture Units)
Cold
Hot
Total
Water
Closet
Public/Private
Flush Valve
10
–
10
Water
Closet
Public/Private
Flush Tank
3
–
3
Urinal
Public
1" Flush
Valve
10
–
10
Urinal
Public
¾" Flush
Valve
5
–
5
Urinal
Public
Flush Tank
3
–
3
Lavatory
Public
Faucet
1
1
2
Bathtub
Public
Faucet
3
3
4
Shower Head
Public
Mixing Valve
2
2
3
Service
Sink
Offices, etc.
Faucet
2
2
3
Kitchen
Sink
Hotel/Restaur.
Faucet
3
3
4
Drinking
Fountain
Office, etc.
3/8"
Valve
0.25
–
0.25
Lavatory
Private
Faucet
0.75
0.75
1
Bathtub
Private
Faucet
1.5
1.5
2
Shower
Stall
Private
Mixing Valve
1
1
2
Kitchen
Sink
Private
Faucet
1.5
1.5
2
Laundry
Trays (1 to 3)
Private
Faucet
2
2
3
Dishwashing
Machine
Private
Automatic
-1
1
Laundry
Machine (8 lb)
Private
Automatic
1.5
1.5
2
Laundry
Machine (16 lb)
Public/ General
Automatic
3
3
4
Agency Notes: For fixtures not listed, loads shall be assumed by
comparing the fixtures to one listed using water in similar quantities and at
similar rates. The assigned loads for fixtures with both cold and hot water
supplies are given for separate cold and hot water loads and for total load.
Where a unit of
local government or the community public water supply does not require separate
water service lines for irrigation or similar systems that are likely to impose
continuous demands (e.g., lawn sprinkler or air conditioning systems), the
following rule applies: estimate the continuous demand (in gallons per minute)
for outlets/systems separately from the intermittent demand from the fixtures
listed in this table, and add this amount to the demand of the fixtures (in
gallons per minute).
Fire sprinkler
systems are exempt from this table.