77 Ill. Adm. Code 905.80
Re-circulating Sand Filter
Section 905
Section 905.80Â Re-circulating
Sand Filter
a)        General. The re-circulating sand filter system (Appendix A,
Illustration O) consists of a septic tank, recirculation tank, open sand filter
and flow splitter. It may be used provided that the effluent is discharged in
accordance with the requirements of Section 905.110.
b)        Septic Tank. The septic tank shall be sized and installed as
described in Section 905.40.
c)        Re-circulation Tank. The re-circulation tank volume shall be
500 gallons, and the tank shall be equivalent in strength and materials to the
septic tank as provided in Section 905.40. No baffles are necessary. An
access manhole, as described in Section 905.40(b)(7), shall be provided for
pump maintenance or replacement.
d)        Sand Filter. The sand filter shall be sized at one square
foot of filter surface for every 3 gallons per day of domestic sewage flow.
Appendix A, Illustration P has a size chart for residences based on numbers of
bedrooms. Unless otherwise stated in Appendix A, Illustration P, the sizes
shown are required. The filter media shall comply with requirements of Section
905.70(e) and (f) and shall be 30 inches in depth.
e)        Bedding Material. The bedding material for the collection
lines shall be the same as that in a buried sand filter. The coarse gravel
shall be ¾ to 2½ inch diameter, and the pea gravel shall be from ⅛ to ⅜
inches diameter. A minimum of 2 inches of coarse gravel shall be placed on the
excavation prior to placement of collection lines.
f)        Distribution and Collection Lines. The collection lines shall
be constructed of materials as approved in Section 905.20(f) and shall be 4
inches inside diameter perforated piping laid with perforations facing
downward. The distribution piping shall have an inside diameter of 1½ inches.Â
The perforated pipe shall have ½ to ¾ inch diameter openings on 3-inch to 5-inch
centers with 2 rows at 120° from each other. Distribution piping shall be
spaced on 3-foot centers and shall be located a minimum of 1½ feet from
sidewalls.
g)        Pumps. The pump shall be a submersible pump designed for
corrosive liquids and shall have a capacity of 15 to 25 gallons per minute at
the 10-foot total dynamic head (TDH). The pump shall be controlled by a time
clock that can be set to activate the pump at one hour or longer intervals.Â
Pump shut-off shall be controlled by a low level float switch that allows the
entire contents of the re-circulation tank to be pumped during each pump
cycle. A high level float switch shall be provided that energizes a visible
and audible alarm to indicate pump failure or malfunction. (See Appendix A,
Illustration Q.)
h)        Flow Splitter. The flow splitter shall be designed so that re-circulation
rates can be controlled between no re-circulation and a 5:1 re-circulation
ratio. An example of one type of splitter is shown in Appendix A, Illustration
O.