77 Ill. Adm. Code 905.95
Illinois Raised Filter Beds
Section 905
Section 905.95Â Illinois
Raised Filter Beds
a)Â Â Â Â Â Â Â Â Illinois raised filter bed disposal systems shall have a
filter loading rate of 4 gallons per square foot per day for residential
systems of up to 1,500 GPD flows. Non-residential systems of any size or residential
systems in excess of 1,500 GPD shall use a filter loading rate of 2.5 gallons
per square foot per day. The system shall be designed in accordance with
Appendix A, Illustration X, Exhibits A through E.
b)Â Â Â Â Â Â Â Â An aeration batch treatment system that has been approved by
NSF in accordance with NSF Standard 40 shall be used. The aeration tank volume
shall hold at least 2 times the average daily wastewater flow for residential
use (including the use of a garbage disposal). Non-residential systems shall
have a tank volume size of 3 times the daily wastewater flow. Multiple tanks
shall be used to achieve the volume required. Multiple tanks require
connection at the bottom of each tank for flow equalization.
c)        Filter beds shall not exceed 600 square feet. If a larger
area is needed, multiple beds shall be used, separated by a minimum distance of
15 feet, using a common mantle. The filter beds can be placed at any point on
the mantle to accommodate existing ground contours.
d)Â Â Â Â Â Â Â Â The filter length shall not exceed 3 times the width.
e)Â Â Â Â Â Â Â Â The sand filter media shall have an effective size of 0.5 to
2.0 millimeters, a uniformity coefficient of less than 3.5, and a 30-inch
depth.
f)Â Â Â Â Â Â Â Â The mantle shall be sized in accordance with the formula A =
QT/25, where A = Mantle Area, Q = Quantity of wastewater per day, and T =
Percolation time of the original soil in minutes per inch. (See Appendix A,
Illustration X, Exhibit E to convert soil investigation information to T (percolation
time).)
g)Â Â Â Â Â Â Â Â The mantle shall be at least equal to the area of the filter
bed. The mantle shall not be designed for percolation rates that exceed 120
minutes per inch.
h)Â Â Â Â Â Â Â Â The mantle area is to be cut into original soil to a depth of
6 inches and back-filled with 12 inches of torpedo sand that is graded as
FA1-FA8 in accordance with Standard Specifications for Road and Bridge
Construction (Illinois Department of Transportation).
i)Â Â Â Â Â Â Â Â Â The slope of the bottom of the mantle shall be level, plus or
minus one inch. The slope of the earth sidewalls of the filter shall be a
maximum of 3 feet horizontal to one foot vertical.
j)         The mantle area shall be at least 12 inches deep. If the
maximum high groundwater table is less than 6 inches from the bottom of the
filter bed, additional torpedo sand shall be used to increase the isolation
distance between the bottom of the filter bed and the high groundwater table to
at least 6 inches. Other separation distances (e.g., well, property line)
shall be measured from the toe of the filter bed.
k)Â Â Â Â Â Â Â Â The distribution piping (4-inch perforated pipe) shall be
placed level to 15-inch centers in 12 inches of ¾-inch stone.
l)Â Â Â Â Â Â Â Â Â Sod shall be placed over the filter beds and mantle.