77 Ill. Adm. Code 920.40
Design Factors
Section 920
Section 920.40Â Design
Factors
The design of each
well shall include the following:
a)        Natural Protection. Location of the well shall include use of
every natural protection available to promote sanitary conditions.
b)        Geologic Formations. The well construction shall be adapted
to the geologic formations and groundwater conditions at the site, but shall
comply with this Part.
c)        Undesirable Geologic Formations. Water-bearing formations
shall be excluded by installing casing or a liner and properly sealing when the
formations contain undesirable water. When a contaminated formation is to be
excluded, the liner shall be grouted in place, in accordance with Section
920.90(h), from 10 feet below the bottom of the contaminated formation to at
least 10 feet above the top of the contaminated formation. When multiple
water-bearing formations of different static water levels are penetrated in the
construction of a water well and the lower water-bearing formation has
sufficient yield for the water well, the upper water-bearing formations shall
be excluded by installing casing or a liner and properly sealing to prevent the
dewatering of the upper water-bearing formations.
d)        Capacity. The well shall be capable of producing as much of
the desired water quantity as the aquifer or aquifers can safely furnish.
e)        Durability. Construction methods and materials shall provide
a durable well capable of maintaining safe water and protecting the aquifer.
f)        Pitless Well Adapters. No well casing shall be cut off or cut
into below ground surface except to install a pitless well adapter below the
frost level. Pitless well adapters or pitless units installed on plastic well
casing shall be pressurized at the point of attachment with the well casing,
unless the pitless unit is solvent welded onto the plastic casing and the riser
casing of the pitless unit is plastic. Pitless well adapters installed on
steel well casing shall be pressurized at the point of attachment with the well
casing, unless the pitless unit is threaded or welded onto the well casing. Â
The annular opening between the well casing and the well borehole or any
excavation made to install the pitless adapter shall be filled with earth to
minimize settling and shall be mounded to provide drainage away from the well.Â
The contractor installing the pitless well adaptor shall be responsible for the
installation of the earth backfill. A list of approved pitless well adapters
will be periodically updated and a copy of this list may be obtained from the
Department.
g)        Well Caps. There shall be no openings through the well cap
except for a factory-installed vent, air line connection, and power supply wiring
unless a proposal is submitted to and approved by the Department. The proposal
shall show that any entrance into the well cap is watertight. In addition,
well caps shall:
1)Â Â Â Â Â Â Â Â Prevent surface water from entering the water supply;
2)Â Â Â Â Â Â Â Â Be secured in position;
3)Â Â Â Â Â Â Â Â Be removable only with tools; and.
4)Â Â Â Â Â Â Â Â Be resistant to weathering and corrosion.
h)        Chemical Injection System. Where a chemical injection system
is directly connected to a water well used for irrigation, a backflow device
shall be installed in accordance with Section 925.40 of the Illinois Water Well
Pump Installation Code.
i)         Vents. Vent piping shall be of adequate size to allow
equalization of air pressure in the well. For wells that are greater than 4
inches in diameter, the vent shall be not less than ½ inch in diameter. Vent
openings shall be located so as to prevent contamination of the well and shall
be reasonably tamper proof. The vent opening shall be turned down, secured in
position, and screened with not less than 24-mesh durable screen or filtered so
as to prevent the entry of insects. The vent opening shall terminate at least
8 inches above finished grade, or 24 inches above maximum high water level in
areas where flooding occurs. Â Wells shall be properly vented in areas where
toxic or inflammable gases are known to be a characteristic of the water. If
either of these types of gases are present, all vents located in buildings
shall be extended to discharge outside of the building at a height where the
vent will not be a hazard. Venting is required on all wells except driven
water wells and flowing wells.