77 Ill. Adm. Code 920.Table
C Minimal Lateral Distances in Feet Between Water Wells, Closed-Loop Wells, and Sources of Contamination
Section 920.Table CÂ Â Minimal Lateral Distances in Feet
Between Water Wells, Closed-Loop Wells, and Sources of Contamination
SOURCES OF
CONTAMINATION
OR EXISTING
WATER WELL
MINIMUM LATERAL
DISTANCES FOR CLAY AND LOAM SOILS (FEET)
WATER
WELL
CLOSED
LOOP WELL
Cesspool
150
150
Closed Loop
Well
1
200
NA
Water Well
1
NA
200
Water Well (when the owner of the closed loop well and a
water well serving a private water supply is the same)
1
N/A
75
Leaching Pit
100
100
Pit Privy
75
75
Subsurface Seepage System, Distribution Box, Sand Filter,
Waste Stabilization Pond, Effluent Receiving Trench
75
75
Manure Pile
75
75
Septic Tank, Aerobic Treatment Plant, Surface Discharge
Effluent Line, Treated Effluent Discharge Point
50
50
Barnyard or Animal Confinement Lot
50
50
Footing Drains (No connection to a sewer or sump handling
sewage is allowed.)
10
10
2
Pump House Floor Drain
2
2
2
Pit, Crawl Space or Basement
5
5
2
Lake, Pond or Stream
25
25
3
Potential Primary Source, Potential Secondary Source, or
Potential Route
200
200
Potential Primary Source, Potential Secondary Source, or
Potential Route (when the owner of the source or route and a water well
serving a private water supply or closed loop well is the same)
75
75
Abandoned Wells
200
200
Sewers (Sanitary or Combined)
50
4
50
4,5
Storm Sewers
10
10
6
1
A
closed loop well utilizing USP food grade propylene glycol may be located to
within 25 feet of a water well.
2
These
setbacks do not apply when the closed loop well is installed prior to the
construction of the building.
3
The
25-foot separation distance from a pond does not apply to a closed loop well
when:
1)Â Â Â The borehole is grouted the
same day that is constructed;
2)Â Â Â The top
20 feet of the borehole is bored to a diameter at least 3 inches greater than
the total diameter of the heat exchanger; and
3)Â Â Â The
enlarged top 20 feet of the borehole is grouted with bentonite chips
manufactured for well sealing within 24 hours after the construction of the
borehole.
4
A
water well or closed loop well may be located to within 10 feet of a sewer
provided that the sewer consists of cast iron pipe with watertight mechanical
joints or rubber gasket sealed joints that meet ASTM Standard C564-11, SDR 26
PVC pipe or schedule 40 PVC pipe or heavier with solvent welded watertight
joints or elastomeric seals (gaskets) used for push-on joints that meet ASTM
Standard F477-10.
5
If
the sewer pipe material is unknown, the 50-foot separation distance may be
reduced to 25 feet if the following conditions are met:
1)Â Â Â The
borehole is grouted the same day that it is constructed;
2)Â Â Â The top
20 feet of the borehole is bored to a diameter at least 3 inches greater than
the total diameter of the heat exchanger; and
3)Â Â Â The enlarged
top 20 feet of the borehole is grouted with bentonite chips manufactured for
well sealing within 24 hours after the construction of the borehole.
6
The
10-foot separation distance for a storm sewer does not apply to a closed loop
well when:
1)Â Â Â The borehole is grouted the
same day that it is constructed;
2)Â Â Â The top
20 feet of the borehole is bored to a diameter at least 3 inches greater than
the total diameter of the heat exchanger; and
3)Â Â Â The
enlarged top 20 feet of the borehole is grouted with bentonite chips
manufactured for well sealing within 24 hours after the construction of the
borehole.