77 Ill. Adm. Code 930.30
Treatment Plant Operation
Section 930
Section 930.30Â Treatment
Plant Operation
a)Â Â Â Â Â Â Â Â Slow sand filtration plants shall comply with the following.
1)        Disinfection of Storage Tank. The walls and bottom of the
storage tank must be free of dirt and debris prior to operation. The side and
bottom must then be washed with a chlorine solution of 100 parts per million.
2)Â Â Â Â Â Â Â Â Prior to operation, the filter must be disinfected with a
solution of 100 parts per million. The effluent valve is to be closed, and
this solution must remain in the filter for at least 24 hours.
3)Â Â Â Â Â Â Â Â Before water is allowed to flow to the filter, a clean piece
of wood, fiberglass or a metal plate 2 feet square must be placed on the
surface of the sand in order to prevent the initial water from disturbing the
sand. After the filter has reached operating level, the plate must be removed.
4)        Filtration Rate. The filtration rate shall not exceed 2
gallons per minute for each 25 square feet of sand filter area.
b)Â Â Â Â Â Â Â Â Cartridge
filtration treatment plants shall comply with the following.
1)Â Â Â Â Â Â Â Â The flow rate shall not exceed the maximum design flow rate
for any of the filters or disinfection system.
2)Â Â Â Â Â Â Â Â The water pressure shall be maintained at 20 pounds per square
inch or greater downstream of the treatment plant.
c)Â Â Â Â Â Â Â Â Disinfection
shall comply with the following.
1)Â Â Â Â Â Â Â Â If chlorine disinfection is used, a minimum free chlorine
residual of at least 0.2 mg/L shall be maintained at distant points in the
water distribution system and a minimum free chlorine residual of 0.4 mg/L
shall be maintained in the water storage tank.
2)Â Â Â Â Â Â Â Â If ultraviolet disinfection is used, the ultraviolet
disinfection equipment shall be kept in continuous operation 24 hours per day.