77 Ill. Adm. Code 935.85
Electrical
Section 935
Section 935.85Â Electrical
a)Â Â Â Â Â Â Â Â New Installations. Electrical wiring and appurtenances
installed between January 1, 1990 and July 1, 1997 shall comply with the 1990
edition of the National Fire Protection Association's National Electrical
Code. Electrical wiring and appurtenances installed after July 1, 1997 shall
comply with the 1996 edition of the National Electrical Code. (A)
b)Â Â Â Â Â Â Â Â Existing Installations. Electrical wiring and appurtenances
installed prior to January 1, 1990 shall comply with the following:
1)Â Â Â Â Â Â Â Â The type and size of all conductors shall comply with the
National Electrical Code in existence at the time of installation. (B)
2)Â Â Â Â Â Â Â Â All electrical distribution systems shall be protected against
over-current by circuit breakers or fuses sized for the rated capacity of the
conductors. Fuses and circuit breakers shall not have a larger rating than the
receptacles they protect. (B)
3)Â Â Â Â Â Â Â Â There shall not be any open ground on any three wire system,
open neutral, open hot conductors or reversed wiring conditions. (A)
4)Â Â Â Â Â Â Â Â All electrical connections shall be in accordance with the
National Electrical Code in existence of the time of installation. No wiring
shall be exposed that could cause personal injury. (B)
c)Â Â Â Â Â Â Â Â Maintenance. All electrical equipment shall be installed and
maintained in accordance with the manufacturer's requirements. (B)
d)Â Â Â Â Â Â Â Â Lighting. Artificial lighting equivalent to one watt of
incandescent light per square foot of floor area shall be provided in all rooms
except toilet rooms which shall be provided an equivalent of one half watt per
square foot. Exterior lighting shall be provided for the entrance to all
buildings which are part of the camp. (C)