83 Ill. Adm. Code 460.360
Testing Facilities and Equipment
Section 460
Section 460.360 Testing
Facilities and Equipment
a) Each MSP shall provide a meter shop adequately equipped with
reference standards, instruments and other facilities, equipment, and personnel
necessary to make the tests required of the MSP by this Part. Each MSP shall
provide working standards and portable standards necessary to make the tests
required of the MSP by this Part. All apparatus and equipment shall be
available at all times during the MSP's established business hours for the
inspection of or use by authorized representatives of the Commission. If meters
used for billing and maintaining customer usage data are tested at a facility
located outside this State, the MSP shall take precautions to insure that the
meters are not damaged in transit to or from that testing facility.
b) Each MSP shall verify the accuracy of all reference standards
at least once every twelve months. If the comparison indicates that the
reference standard is in error by more than 0.5% on any combination on which it
will be used, the MSP shall adjust the standard to reduce the inaccuracy, if
possible. In any case, the MSP shall apply the correction indicated by the
certificate or calibration card accompanying the instrument (pursuant to
subsection (d)).
c) When in use for testing meters, all solid state working and
portable standards shall be compared to a reference standard at least once
every six months. All other working and portable standards used regularly for
testing meters shall be compared to a reference standard at least once every
month. When working or portable standards are used for purposes other than
testing meters, they shall be compared to a reference standard at least once
each year. If found in error by more than 0.5%, the MSP shall adjust the
instrument to read within the specified limits or shall apply the proper
correction factor.
d) Each working, portable or reference standard shall be
accompanied at all times by a certificate or calibration card signed or
initialed by the person responsible for the calibration giving the date and
results of the last calibration of the instrument. The MSP shall keep any
superseded certificates or calibration cards on file for at least three years.
e) An authorized representative of the Commission may check or
establish the accuracy of all testing equipment owned by each MSP that is used
for testing metering equipment used or intended for use in this State, as well
as the methods of operating such equipment. An authorized representative of the
Commission shall perform an audit of each MSP's testing equipment and methods at
least every three years. The MSP shall reimburse the Commission for all
expenses related to audits of meter shops used or maintained by the MSP located
outside this State.