83 Ill. Adm. Code 460.510
Illinois Class 1 Qualification
Section 460
Section 460.510 Illinois
Class 1 Qualification
a) Metering Types and Voltages. Workers with an MSP Class 1
Qualification are permitted to perform work on single-phase, socket-based
meters, operating at a maximum of 120/240 volts or 120/208 volts. This level of
qualification does not include transformer-rated meters. Also, connections of
meter communications devices shall be outside of energized meter panels.
b) Work to be Performed. MSP Class 1 meter workers may install,
remove and replace single-phase, 120/240 volt or 120/208 volt self-contained
meters in standard socket-based metering installations. Connections for
communication conductors shall be outside the energized meter panels. MSP Class
1 meter workers may be required to install jumpers on single-phase services
where bypass provisions are provided or operate a manual bypass switch to
maintain service continuity where applicable.
c) Safety Skills
1) Knowledge of basic electrical theory and associated hazards
and ability to perform work while avoiding hazards; and
2) Knowledge of and ability to perform work in compliance with
procedures and safety rules applicable to class of work performed, including:
A) Basic safety (e.g., driving hazards and animal bite
prevention);
B) Electrical safety;
C) OSHA requirements;
D) State requirements;
E) Personal protective equipment;
F) Distribution safety procedures.
d) Essential Technical Skills
1) Knowledge of basic AC/DC electrical theory;
2) Knowledge of single-phase electrical metering;
3) Knowledge of electric distribution in general;
4) Knowledge of the meter panel and socket layout for the
metering conditions of this class of meter work;
5) Ability to identify energy diversion or tampering related to
this class of meter work;
6) Ability to install and remove damaged and undamaged meters;
7) Ability to read meters used in this class;
8) Ability to use tools appropriate to this class of work;
9) Ability to connect meter communications external to the meter
panel;
10) Customer contact skills;
11) Ability to distinguish between single-phase and poly-phase
services;
12) Knowledge of DSP construction standards and local inspection
authority requirements;; and
13) Ability to safely jumper single-phase meter sockets to
maintain service continuity.
e) Determination of Essential Technical and Safety Skills
1) MSPs shall develop and implement a program to train workers to
perform Class 1 meter work safely and properly;
2) A minimum of 500 hours on the job training with a Class 1
meter worker (with at least 1 year of experience as a Class 1 meter worker) or
with a meter worker with a higher classification and successful completion of
the MSP classroom training program.
f) Meter Worker Certification and Re-certification Requirements
1) Employees are certified by the certified MSP, based on
successful completion of the training program referenced in subsection (e),
demonstrated ability to perform Class 1 meter worker safety skills and
essential technical skills, and prior experience;
2) A Class 1 meter worker who has not performed metering work
equivalent to that described in subsection (b) for six months or more shall be
re-certified prior to performing Class 1 meter work.