83 Ill. Adm. Code 535.200
Work Performed on Regulators and Manometers
Section
535.200 Work Performed on Regulators and Manometers
a) Prior
to performing work at a customer location on a mercury-containing regulator or
manometer used in providing natural gas service, a public utility shall test
the air for mercury vapor in at least two locations: one location one foot
above or away from the regulator or manometer and another location within three
to five feet above the floor for indoor meters, or three to five feet above
ground level for outdoor meters, immediately adjacent to the regulator or
manometer.
b) After
performing the work on a mercury-containing regulator or manometer used to
provide natural gas service, a public utility shall test the air for mercury
vapor at the same locations used for air sampling prior to performing the work
on the regulator or manometer.
c) A
public utility shall consider a confirmed reading at, or in excess, of the
following levels as a positive indication of mercury.
1) 0.003
milligrams (3 micrograms) per cubic meter of air for mercury vapor air sample
tests conducted inside of a residential customer location.
2) 0.010
milligrams (10 micrograms) per cubic meter of air for mercury vapor air sample
tests conducted at non-residential locations and outside of a residential
customer location.
d) When
testing for mercury vapor, a public utility shall use mercury vapor testing
equipment capable of detecting the presence of mercury at the levels required
by subsection (c).
e) A
public utility shall use mercury vapor testing equipment in accordance with the
guidelines set forth by the manufacturer of the equipment.
f) A
public utility shall not perform any mercury vapor air sample tests under
conditions that would counter the manufacturer’s recommendations for use of the
mercury vapor test equipment except for the following reasons:
1) A
public utility may perform work on mercury-containing regulators or manometers
located outdoors without conducting the required mercury vapor test if
conditions are not suitable for accurate readings from its mercury vapor test
equipment, but shall return to the work site and test for mercury vapor as soon
as conditions are favorable for accurate readings from its mercury vapor test
equipment; or
2) In an
emergency, as defined in Section 535.10, a public utility may perform work on
mercury-containing regulators or manometers without conducting the required
mercury vapor test, if conditions are not suitable for accurate readings from
its mercury vapor test equipment, but shall return to the work site and test
for mercury vapor as soon as conditions are favorable for accurate readings
from its mercury vapor test equipment.