83 Ill. Adm. Code 730.305
Maintenance of Plant and Equipment
Section 730
Section 730.305 Maintenance
of Plant and Equipment
Each local exchange carrier
shall:
a) adopt
a maintenance program for its equipment based on the minimum standards set
forth in this Part, which program shall be updated regularly but not less than
every two years unless an earlier update is requested by the Commission.
b) inspect
every two years, in accordance with the National Electric Safety Code (NESC)
standards identified in 83 Ill. Adm. Code 305, its electrical grounding
equipment owned by such carrier for each central office, including, without
limitation, the component of such system commonly known as the master ground
bar, to ascertain the integrity of the central office ground field, and
maintain a copy of the test results in the office and available for inspection.
The inspection shall be performed
annually if one of the following events occurs: an office conversion
(replacement of the current switching equipment), a building addition to a
central office, or renovations to the building facilities and grounds, such as
water, sewer, gas, electric facilities or parking lot.
c) copy,
on a monthly basis, its database for switching equipment applicable to each
central office and store such copy off-site or in a fireproof on-site storage
for use in emergency restoration purposes (such copying and storage to be
performed in accordance with current software backup procedures).
d) copy,
on a monthly basis, its digital access and cross-connect system (DACS) database
for each central office, if technically feasible, and store such copy off-site
or in a fireproof on-site storage for use in emergency restoration purposes
(such copying and storage to be performed in accordance with current software
backup procedures).
e) copy,
on a monthly basis, its fiber optic terminal database for each central office,
if technically feasible, and store such copy off-site or in a fireproof on-site
storage for emergency restoration purposes (such copying and storage to be