83 Ill. Adm. Code 737.410
Emergency Operation
Section 737.410 Emergency Operation
a) Each Local
Provider shall make provisions to meet emergencies resulting from failures of
commercial or power service, sudden and prolonged increases in traffic, illness
of personnel, fire, storm, or other natural disasters. Each Local Provider
shall inform employees of the procedures to be followed in the event of an emergency
in order to prevent or minimize interruption or impairment of
telecommunications service.
b) Each
existing central office will contain a reserve battery supply of 5 hours when
emergency power generators are not installed and 3 hours when they are in
place. Central office batteries shall be maintained in accordance with Institute of Electrical and Electronic Engineers (IEEE) standards as adopted in Section
737.420, and records verifying maintenance shall be kept on site. New central
offices or central offices being replaced shall contain a reserve battery
supply of 8 hours when emergency power generators are not installed and 5 hours
when they are in place. In central offices without installed emergency power
generators, a mobile power unit shall be available that can be delivered and
connected within 5 hours.
c) In
new central offices exceeding 3,000 working lines, a permanent power generator
shall be installed. For existing central offices having over 3,000 lines,
permanent power generators shall be installed at the time of office replacement
or battery replacement.
d) Emergency
generator units shall have available at least a 12 hour fuel supply.
e) Emergency
generator units shall be tested under load once a month. A record of the test
results shall be maintained.
f) The
requirements of subsections (b) through (e) apply to a Local Provider only to
the extent that it owns and/or operates central offices.