83 Ill. Adm. Code 785.55
Technical Requirements
Section 785
Section 785.55 Technical
Requirements
a) Power and Communications Systems
1) All direct current (DC) power supply service feeds shall be
fused at a level not to exceed the rated capacity of the smallest conductor
used in the feed, or 200% of the maximal operational consumption of the feed,
whichever is smaller.
2) The use of equalizing center design, the practice of tapping
smaller power cables to larger power cables, is only permitted when fused at
the tap, or fused in accordance with subsection 785.55(a)(1) above.
3) Main power supply systems, both AC and DC, shall be designed
to enable a practical, safe disconnection of all interior feed circuits using a
master or zoned master switches or fuses. Multiple locations for zoned master
switches or fuses may be utilized, but no more than three locations per floor
shall be permitted except that existing telecommunications switch facilities
with multiple power supply systems exceeding three locations per floor shall
develop and utilize a coded layout plan for effective zoned disconnections
subject to individual approval by the Office of the State Fire Marshal.
Details of such disconnect plan shall be made a part of the pre-emergency plan.
4) Carriers should consider the incorporation of surge protective
devices for use on AC service to mitigate the potential impact of equipment
damage due to transient or overvoltage surges.
5) Armored cable, rigid or flexible metal conduit, or any other
cable with an exterior metallic or conductive external surface shall not be
placed in cable trays containing AC, DC or communications cables.
6) Wherever possible, existing AC and DC power cables should be
physically separated from communications cables. New construction shall have
AC and DC power cables physically separated from communications cables.
7) Use of cables employing polyvinyl chloride (PVC) insulation
for any new or expansion of facilities shall be allowed only if the cable has
an oxygen index rating of 28 or higher, unless monitored by a system designed
to sense chloride emissions.
8) Removal of old cable shall be monitored by each telephone
company or telecommunications carrier to guard against damage to remaining
cable.
b) Detection Systems
1) Design and installation shall comply with fire protection
standards as published in the NFPA's Code 72 and 72E.
2) Types of fire detectors include heat, smoke, flame, laser,
photo-electric, aspiration, ionization and fire-gas types. Detection systems
shall utilize a minimum of two (2) types of devices monitoring each alarm zone
within a facility for buildings exceeding 1,600 square feet. Buildings of less
than 1,600 square feet will require one (1) single detector-type capability.
Single detector-type systems shall not utilize heat only sensors.
3) Each facility with multiple alarm zones within a building
exceeding 1,600 square feet shall have a local interior zone annunciator panel
immediately inside of an entrance door as designated in the pre-plan. The
facility may also have remote monitoring by a company operated central
station. Upon receipt of fire signal at such remote station, the station
operator shall immediately notify the appropriate Fire Department.
4) Each carrier should develop a facility inspection program
utilizing thermographic infrared scanning technology or equivalent as an aid to
identify abnormal heat buildup.
c) Ventilation
1) All facilities shall provide ventilation access for removal of
smoke and toxic gases from the facility as follows:
A) Single level telephone facilities consisting of no more than
1,600 square feet shall provide no less than two separate physical openings of
sixteen (16) square feet each or greater on separate sides of the facility
unless the local fire agency agrees to accept a single opening.
B) All facilities exceeding 1,600 square feet (including
multi-story buildings) shall provide at least two (2) vent access openings per
floor. The minimum size of each opening shall be sixteen (16) square feet for
each 10,000 square feet of floor area, except that multiple vent openings per
floor shall not be required where mechanical smoke evacuation systems are
present and are acceptable to the local fire agency.
d) Suppression
1) Automatic discharge systems containing water, dry chemical,
foam or other suppression agents shall not be required in rooms housing switching,
toll, main distribution frame, power, auxiliary power and AC switchboard
equipment.
2) Suppression systems utilizing sprinklers or Halon shall be
provided in cable vault areas and other areas not excluded by subsection
785.55(d)(1) above, except that no suppression systems are required for
telecommunications buildings less than 1,600 square feet.
e) Inspections
1) The Agencies shall be permitted to inspect all facility
locations for compliance.
2) Each carrier shall permit the fire department or fire
protection district to conduct an annual inspection of each telecommunications
facility. The local fire department shall have the option of inspecting more
than once a year if it so requests. Fire departments with full-time staff shall
be allowed to conduct an inspection for each of the three shifts, if requested.