8 Ill. Adm. Code 215.110
Systems Mounted on Implements of Husbandry for the Transportation of Anhydrous Ammonia
Section 215
Section 215.110 Systems
Mounted on Implements of Husbandry for the Transportation of Anhydrous Ammonia
All of Section 215.25 shall
apply to this Section unless otherwise stated.
a) This Section
applies to containers of 3000 gallons water capacity or less and related
equipment mounted on nurse tanks that are used for the transportation of
ammonia.
1) Any
nurse tank that does not have a legible data plate and has not been recertified
in conformance with Transportation Regulations (see Section 215.16) shall be
removed from service.
2) Any
container
or combination of containers on a
single running gear, greater than 3000 gallons, that are used for the
transportation of anhydrous ammonia and to supply the application device shall
be prohibited. This shall exclude cargo tanks used for transportation only.
b) Containers
shall be constructed in accordance with Section 215.25. The shell or head
thickness of any container shall not be less than
3
/
16
of
an inch. All containers over 500 gallons capacity should be equipped with
semi-rigid baffle plates.
c) A
suitable "stop" or "stops" shall be mounted on the farm
wagon or on the container in such a way that the container shall not be
dislodged from its mounting due to the farm wagon coming to a sudden stop.
Back slippage shall also be prevented by proper methods.
d) A
suitable "hold-down" device shall be provided that will anchor the
container to the farm wagon at one or more places on each side of the
container.
e) When multiple
containers are mounted on a running gear, the weight shall be distributed appropriately
over the axles. Multiple containers mounted on the same running gear must be
of the same capacity. All manual shutoff valves shall be located behind the
steel bulkhead or permanently affixed in a secure point to provide equivalent
protection of the piping from that point to the front of the tank.
f) When
the cradle and the container are not welded together, suitable material shall
be used between them to reduce abrasion.
g) All containers shall be
equipped with a fixed maximum liquid level gauge.
h) All
containers shall be equipped with a pressure gauge having a dial graduated from
0 psi to 400 psi.
i) The
filling connection of each container shall comply with the requirements of
Section 215.40(j).
j) All
containers shall be equipped with an approved vapor-equalizing valve unless
equipped for spray loading.
k) All
vapor and liquid connections, except pressure relief valves and those
specifically exempt in Section 215.40(e) and (f) shall be equipped with
approved excess flow valves or may be fitted with quick-closing internal valves
that shall remain closed except during operating periods. Every tank
withdrawal valve shall be protected by an excess flow valve matched to the
designed flow rate. Flow capacity of the excess flow valve shall not exceed 45
GPM for 1¼" tank connections and 60 GPM for 1½" tank connections. When
using an open yoke type excess flow withdrawal valve in a tank opening, the
opening shall not be reduced with bushings to accommodate the withdrawal valve.
Each valve shall be tested through the Nurse Tank Inspection Program (NTIP) or be
removed and inspected at an interval not to exceed 5 years. Records of the
maintenance and inspections shall be kept at the facility for review. All
valves shall be in compliance no later than December 31, 2020. Nurse tanks not
meeting compliance shall be removed from service.
l) Fittings
shall be protected from physical damage by means of a rigid guard designed to
withstand static loading in any direction equal to twice the weight of the
container and lading using a safety factor of 4 based upon the ultimate strength
of the material used. If the guard encloses the pressure relief valve, the
valve shall be properly vented through the guard.
m) If a
liquid withdrawal line is installed in the bottom of a container, the
connections to that line, including hose, shall not be lower than the lowest
horizontal edge of the farm wagon axle. The hose shall be drained and
depressurized prior to the container being moved or towed on a public road.
n) Provision shall be made
to secure both ends of the hose in transit.
o) All containers shall be
painted white or a light reflecting color.
p) All containers shall be
marked as follows:
1) Placard:
Four diamond type, nonflammable gas, UN 1005, USDOT placards shall be
displayed (one on each side and one on each end).
2) Marking:
The words ANHYDROUS AMMONIA shall appear on each side and each end in letters
no less than 2 inches high.
3) Each
container shall be marked with the words INHALATION HAZARD in 2 inch letters on
2 opposing sides.
4) The
words LIQUID or VAPOR shall be placed on or within 12 inches of the appropriate
valve by means of stencil, tag, decal or color coding with a legible legend
ORANGE LIQUID and YELLOW VAPOR on the tank.
5) The
container need not be marked or placarded on one end if that end contains
valves, fittings, regulators or gauges when those appurtenances prevent the
markings and placard from being properly placed and visible.
q) Nurse
tanks operating on public roads shall be marked with a slow-moving vehicle
(SMV) emblem consisting of a fluorescent orange triangle with a red reflective
border. The specifications of the SMV shall be the type recommended by ASAE
S276.5. Nurse tanks operating on public roads are to travel at speeds less
than 25 mph.
r) All nurse
tanks shall be securely attached to the vehicle drawing them by means of
drawbars supplemented by suitable hitch pins with clips and safety chains permanently
attached to the farm wagon.
s) A nurse
tank shall be constructed so that it will follow substantially in the path of
the towing vehicle and will prevent the towed farm wagon from whipping or
swerving dangerously from side to side.
1) Nurse
tanks require two safety chains with a combined breaking strength of at least
the weight of the laden nurse tank.
2) All
nurse tanks shall be securely attached to the vehicle drawing them by means of
drawbars supplemented by suitable hitch pins and safety chains that meet the
requirements of ASAE S338.2, Safety Chain for Towed Equipment. Reliable
keepers for the hitch pin shall be used to prevent its loss. The hitch pin and
keeper shall be permanently attached to the nurse tank towbar.
t) A nurse
tank shall not be towed or parked in public places such as school yards, malls
or hospital grounds.
u) Each
person operating, repairing appurtenances to, or inspecting a nurse tank shall
wear protective gloves impervious to ammonia and chemical splash goggles. A
full face shield may be worn over the goggles; however, a face shield shall not
be worn as a substitute for a primary eye protection device (goggles).
v) For
first aid purposes each nurse tank shall be equipped with at least 5 gallons of
clean water in a container mounted on top or side of the tank designed to
provide ready access to the water for flushing any area of the body contacted
by ammonia.
w) Prior
to the addition of a chemical additive, its compatibility with system
components shall be verified by the manufacturer of the additive.
x) Storage
of Containers: When a nurse tank containing 10% or more of anhydrous ammonia is
at an unattended approved storage site, the manually controlled valves shall be
plugged or capped or locked or the nurse tank shall be stored inside a locked,
fenced enclosure. Nurse tanks shall be stored no less than 50 feet from the
edge of the adjacent road, 200 feet from place of private or public assembly
and 750 feet from place of institutional occupancy. All pressure and liquid
gauges must be in working order.
y) A
back check valve shall be installed on each inlet of each fitting (including,
but not limited to, tees and crosses) to prevent the back feed of anhydrous
ammonia from an undamaged line to a damaged/severed line. All multiple tank
configurations shall have equally rated liquid withdrawal valves on each tank. An
excess flow valve with the same rated flow as the aforementioned valves shall
be installed at the junction where the lines meet downstream. A shutoff valve
shall be installed downstream of the excess flow valve.
AGENCY NOTE: If tanks are not
plumbed together, they shall be treated as single tanks. Tanks with equally
rated internal valves with remote actuators are exempt from this requirement. Compliance
with these requirements shall be achieved through repairs and modifications on
or before December 31, 2025.
z) Excess
flow valves shall be designed to close automatically at the rated flows of
vapor or liquid as specified by the manufacturer. Excess flow valves shall be
selected based on the piping, including valves, fittings and hoses being protected
by an excess flow valve, and shall have a greater capacity than the rated flow
of the excess flow valve, so the valve will likely close in case of delivery
system failure at any point in the line or fittings. Any installation of a
device that may cause a reduction in pressure to impede the operation of the
excess flow valve is prohibited.
aa) All liquid and vapor service valves shall be protected by a
threaded cap that must be affixed to the valve housing.