8 Ill. Adm. Code 215.115
Systems Mounted on Equipment for the Application of Anhydrous Ammonia
Section 215
Section 215.115 Systems
Mounted on Equipment for the Application of Anhydrous Ammonia
a) This Section
applies to systems mounted on farm equipment and used for the field application
of ammonia. Section 215.25 applies to this Section unless otherwise noted.
b) The
shell or head thickness of any container shall not be less than
3
/
16
of an inch.
c) All
containers shall be securely mounted. Applicators must be secured with hold-down
devices the same way as systems mounted on farm wagons transporting anhydrous
ammonia.
d) Fixed
maximum liquid level gauges shall be used that are designed to indicate when
the container has been filled to 85% of its water capacity. The dip tube of
this gauge shall be installed in such a manner that it cannot be readily
removed.
e) The
filling connection of each container shall comply with the requirements of
Section 215.40(k).
f) An
excess-flow valve is not required in the vapor connection, provided the
controlling orifice is not in excess of
5
/
16
inch in
diameter and the valve is a hand-operated (attached hand wheel or equivalent)
shutoff valve. To assist in filling applicator tanks, it is permissible to
bleed vapors to the open air, provided the preceding requirements are met.
g) Applicators
shall be filled at least 100 yards from any occupied building not on an approved
site.
h) Metering
devices may be connected directly to the tank withdrawal valve. A union-type
connection is permissible between the tank valve and the metering device.
Remote mounting of metering devices is permissible using hoses that meet
specifications.
i) When
the applicator or nurse tank is trailed and the metering device is remotely
mounted, such as on the tractor tool bar, an automatic break-away, self-closing
coupling device shall be used. The coupling device shall be made from or
coated with a corrosion resistant material. The coupling device shall be
mounted in a manner that will permit the device to swivel freely. A coupling
device shall be maintained. An angle valve shall not be used as a hose end
valve connecting to the coupling device.
j) No
excess-flow valve is required in the liquid withdrawal line provided the
controlling orifice between the contents of the container and the outlet of the
shutoff valve (see Section 215.40(c)) does not exceed
5
/
16
in diameter.
k) Any
control valve installed between the regulator and the break-away coupling
device shall indicate whether the valve is open or closed.
l) Where
a ball valve is used to control flow to the metering device, the ball shall be
drilled with an opening smaller than No. 54 (0.055 inches) drill size on the downstream
side to prevent trapping ammonia in the ball when in the closed position.
m) Each
person operating, repairing, or inspecting an applicator shall
wear protective gloves impervious to ammonia and chemical
splash goggles. A full face shield may be worn over the goggles; however, a
face shield shall not be worn as a substitute for a primary eye protection
device (goggles).
n) Each
applicator tank shall be equipped with the following safety equipment and
features: for first aid purposes, at least 5 gallons of clean water in a
container designed to provide ready access to the water for flushing any area
of the body contacted by ammonia and a legible decal depicting step-by-step
ammonia transfer instructions.
o) Instructions
for connecting and disconnecting the coupling device shall be displayed in a
manner as to be readily visible near the break-away coupling device.