8 Ill. Adm. Code 215.70
Liquid Level Gauging Devices
Section 215
Section 215.70 Liquid Level
Gauging Devices
a) Each
container, except those filled by weight, shall be equipped with an approved
liquid level gauging device.
b) Each
container or system covered in Sections 215.85, 215.110, and 215.115 shall be fitted
with a liquid level gauge indicating the maximum level to which the container
may be filled with liquid anhydrous ammonia at temperatures between 20°F and
100°F, except on containers provided with fixed maximum level indicators, such
as fixed length dip tubes or containers that are filled by weight. Marks shall
be in increments of not more than 20°F. See Section 215.60 regarding the requirement
for thermometer well and thermometer.
c) Gauging
devices that require bleeding of the product to the atmosphere, such as the
rotary tube, fixed tube, and slip tube devices, shall be designed so that the
maximum opening of the bleed valve is not larger than No. 54 (0.055 in.) drill
size unless provided with an excess flow valve. (This requirement does not apply
to farm vehicles used for the application of ammonia as covered in Section
215.115.)
d) Gauging
devices shall have a design pressure equal to or greater than the design
pressure of the container on which they are installed.
e) Fixed
maximum liquid level gauges shall be designed and installed to indicate a
volumetric level not to exceed 85% of the container’s water capacity.
Note: This does
not apply to refrigerated storage.
f) Gauge
glasses of the columnar type shall be restricted to stationary non-refrigerated
storage installations. They shall be equipped with shutoff valves having
metallic hand wheels, excess flow valves, and extra heavy glass adequately
protected with a metal housing applied by the gauge manufacturer. They shall
be shielded against the direct rays of the sun.